Page
19
Running in Local
•
On the 890CD keypad select LOCAL mode. The display will show the Local Setpoint : 0.0%
•
Use the UP arrow to set a Local Setpoint, say 20%.
•
Press the green RUN button. The motor will accelerate to the desired speed and maintain it. Adjust
RAMP ACCEL TIME (S3) in Quick Setup to the desired level.
•
Press the red STOP button. The motor will decelerate to a stop. Adjust RAMP DECEL TIME (S4) in
Quick Setup to desired level. If the drive trips on Overvoltage, extend the RAMP DECEL TIME or
connect a braking resistor. Refer to the 890 Engineering Reference Manual.
Go to SYS::SAVE::APP and UP arrow to save your settings Values are stored during power-down.
Running in Remote
•
On the 890CD keypad select REMOTE mode. The display will show the remote Setpoint : ?.?%
(The value displayed depends on the external speed reference).
•
Dial in a speed setpoint using the Speed potentiometer until the display reads 20%.
•
Start the drive by closing the Start contact between terminal X14/03 and terminal X15/02. The
motor will accelerate to the desired speed and maintain it. Adjust RAMP ACCEL TIME (S4) in Quick
Setup to the desired level.
•
Open the Start contact. The motor will decelerate to a stop. Adjust RAMP DECEL TIME (S4) in
Quick Setup to desired level. If the drive trips on Overvoltage, extend the RAMP DECEL TIME or
connect a braking resistor. Refer to the 890 Engineering Reference Manual.
Go to SYS::SAVE::APP and UP arrow to save your settings Values are stored during power-down.
M
M
E
M
E
Содержание 890CS
Страница 9: ...Page 9 Overview...
Страница 27: ...Page 27 890CD Control Terminals...
Страница 28: ...Page 28 890SD Control Terminals...
Страница 29: ...Page 29 890CS Control Terminals...
Страница 30: ...Page 30 Appendix D Electrical Ratings 890CS Common Bus Supply...
Страница 31: ...Page 31 890CD Common Bus Drive...
Страница 32: ...Page 32...
Страница 33: ...Page 33...