6-8
Programming Your Application
650V AC Drive
MMI Parameters Table
Display
Parameter
Description
Range
Default
SET::OUT Menu
AOUT 1 SOURCE
ANALOG OUTPUT
0 NONE
1 DEMAND %
2 CURRENT %
3 PI ERROR %
4 RAISE/LOWER %
SCALE
OFFSET
ABSOLUTE
0-10V
OUTPUT
0= NONE
1= DEMAND
2= CURRENT
3= PID ERROR
4= RAISE/LOWER
OUTPUT
1
AOUT 1 SCALE
+
SCALE
OFFSET
X
VALUE
ABS
X
OUTPUT
100%
0%
CLAMP
-300.00 to 300.00% 100.00%
AOUT 1 OFFSET
-300.00 to 300.00% 0.00%
AOUT 1
ABSOLUTE
0= FALSE
(not absolute)
1= TRUE (absolute)
1
AOUT 1 VALUE
F
-300.0 to 300.0%
0.0%
DOUT 2 SOURCE
Refer to
page 6-6-13.
DIN4 / DOUT2
0 NONE
1 HEALTH
2 TRIPPED
3 RUNNING
4 AT ZERO
5 AT SPEED
INVERT (output)
6 AT LOAD
0= NONE
1= HEALTH
2= TRIPPED
3= RUNNING
4= AT ZERO
5= AT SPEED
6= AT LOAD
0
DOUT 2 INVERT (OUTPUT) As
S
IP01. Set to 0 for applications 1 & 5. As
S
IP01
0
DOUT 2 VALUE
F
The TRUE or FALSE output demand.
0=FALSE
1=TRUE
0
RELAY SOURCE
NONE : Relay is open
Relay is closed when:
HEALTH : the Run signal is not present, or no trip
is active
TRIPPED : a trip is present
RUNNING : the motor is running
AT ZERO : the output frequency is below 1% of
MAX SPEED (
P
2)
AT SPEED : the output frequency is at or near
Setpoint and within ±1% of MAX SPEED, set by
(
P
2)
.
For example: if MAX SPEED = 50Hz and
Setpoint = 30Hz, then 1% of MAX SPEED = 0.5Hz.
So AT LOAD is True between 30 ±0.5Hz.
AT LOAD : the magnitude of the output torque is
greater than or equal to the torque level set in
ST
42
RELAY
0 NONE
1 HEALTH
2 TRIPPED
3 RUNNING
4 AT ZERO
5 AT SPEED
INVERT (output)
6 AT LOAD
As
S
OP21
1
RELAY INVERT
Inverts the value of the signal, TRUE or FALSE.
0=FALSE
1=TRUE
0
RELAY VALUE
F
The TRUE or FALSE output demand.
0=FALSE
1=TRUE
0
Содержание 650V series
Страница 25: ...3 8 Installing the Drive 650V AC Drive Through Panel Cutout Details ...
Страница 27: ...3 10 Installing the Drive 650V AC Drive Duct Kit Installation Diagram ...
Страница 41: ...3 24 Installing the Drive 650V AC Drive Figure 3 16 Gland Box for Footprint Bookcase Mounting Filters generic ...
Страница 55: ...5 6 The Keypad 650V AC Drive ...
Страница 79: ...6 24 Programming Your Application 650V AC Drive ...