![Parker 650V series Скачать руководство пользователя страница 62](http://html.mh-extra.com/html/parker/650v-series/650v-series_technical-manual_755636062.webp)
Programming Your Application
6-7
650V AC Drive
MMI Parameters Table
Display
Parameter
Description
Range
Default
SPEED INT TIME
F
M
SV
This is the integral time constant of the speed loop.
A speed error which causes the proportional term
to produce a torque demand T, will cause the
integral term to also ramp up to a torque demand
T after a time equal to “speed int time”.
1 to 15000ms
product
code
dependent
SPEED POS LIMIT
F
SV
This sets the upper limit of the speed demand.
-110.00 to 110.00% 110.00%
SPEED NEG LIMIT
F
SV
This sets the lower limit of the speed demand.
-110.00 to 110.00% -110.00%
SET::IN Menu
DIN 1 INVERT
Inverts the value of the signal, TRUE or FALSE.
0= FALSE
1= TRUE
0
DIN 2 INVERT
As
S
IP01
As
S
IP01
0
DIN 3 INVERT
As
S
IP01
As
S
IP01
0
DIN 4 INVERT
As
S
IP01
As
S
IP01
0
DIN 5 INVERT
As
S
IP01
As
S
IP01
1
DIN 6 INVERT
As
S
IP01
As
S
IP01
0
DIN 7 INVERT
As
S
IP01
As
S
IP01
0
AIN 1 SCALE
VALUE
+
SCALE
OFFSET
X
INPUT
TYPE
UNPROCESSED
0 to 100% of selected TYPE
-300.0 to 300.0%
100.0%
AIN 1 OFFSET
-300.0 to 300.0%
0.0%
AIN 1 TYPE
0= 0-10V
1= 0-5V
0
AIN 2 SCALE
VALUE
+
SCALE
OFFSET
X
INPUT
TYPE
UNPROCESSED
0 to 100% of selected TYPE
-300.0 to 300.0%
100.0%
AIN 2 OFFSET
-300.0 to 300.0%
0.0%
AIN 2 TYPE
0= 0-10V
1= 0-5V
2= 0-20mA
3= 4-20mA
3
DIN 1 VALUE
F
The TRUE or FALSE input (after any inversion)
0=FALSE
1=TRUE
0
DIN 2 VALUE
F
The TRUE or FALSE input (after any inversion)
0=FALSE
1=TRUE
0
DIN 3 VALUE
F
The TRUE or FALSE input (after any inversion)
0=FALSE
1=TRUE
0
DIN 4 VALUE
F
The TRUE or FALSE input (after any inversion)
0=FALSE
1=TRUE
0
DIN 5 VALUE
F
The TRUE or FALSE input (after any inversion)
0=FALSE
1=TRUE
0
DIN 6 VALUE
F
The TRUE or FALSE input (after any inversion)
0=FALSE
1=TRUE
0
DIN 7 VALUE
F
The TRUE or FALSE input (after any inversion)
0=FALSE
1=TRUE
0
AIN 1 VALUE
F
The input reading with scaling and offset applied
.x%
—
.x%
AIN 2 VALUE
F
The input reading with scaling and offset applied
.x%
—
.x%
Содержание 650V series
Страница 25: ...3 8 Installing the Drive 650V AC Drive Through Panel Cutout Details ...
Страница 27: ...3 10 Installing the Drive 650V AC Drive Duct Kit Installation Diagram ...
Страница 41: ...3 24 Installing the Drive 650V AC Drive Figure 3 16 Gland Box for Footprint Bookcase Mounting Filters generic ...
Страница 55: ...5 6 The Keypad 650V AC Drive ...
Страница 79: ...6 24 Programming Your Application 650V AC Drive ...