![Parker 6053-LINK-00 TechBox Скачать руководство пользователя страница 20](http://html.mh-extra.com/html/parker/6053-link-00-techbox/6053-link-00-techbox_product-manual_756268020.webp)
15
LINK TechBox/TechCard Instruction Manual - HA470016 Issue 5
Chapter 5 - Sample Projects
To demonstrate the use of a
LINK
Technology Option, here are two simple projects consisting of a
584SV drive, with a LA463610U003 TechCard, or 690+ drive with a 6053/6055 TechBox and an
L5392 touchscreen. Our first example uses a 584SV, the second example uses a 690+. By
configuring these pieces, we will build a
LINK
project that will
:
•
Start, stop and jog the drive from the touchscreen
•
Display health status and trips
•
Set line speed
•
Monitor motor speed, frequency, voltage and current
Step 1 – Plan the project
Before any configurations are done, make list of parameters that need to be accessed in the drive.
Go to the “Specification Table – Tag Number Order” section in the drive instruction manual to
identify all tags. For this example they are:
TAG
R / W
Description
Type
Scaling
291
Write
Start Command
Ordinal
-
277
Write
Fast Stop
Ordinal
-
278
Write
Coast Stop
Ordinal
-
294
Write
Reverse Direction
Ordinal
-
280
Write
Jog Command
Ordinal
-
130
Write
Speed Setpoint
Value
1 = 120%
592
Read
Motor Volts
Ordinal
-
70
Read
Motor Load
Value
200% = 1
255
Read
Speed Feedback
Value
120% = 1
6
Read
Drive Status
Ordinal
-
591
Read
Output Frequency
Ordinal
-
52
Read
Drive Healthy
Ordinal
-
285
Read
Drive Running
Ordinal
-
Step 2 – Configure the Drive
584SV/605
Using the drive MMI, preferably ConfigEd Lite, configure the drive as shown in Figure 2. These
instructions will also apply to the 690+ if using ConfigEd. The changes from default are
:
•
Drive Start Command goes to Sequencing Logic\Run Fwd. (Break the default connection
to Run Fwd).
•
Break all input connections to Value Function 1. (Speed Reference goes to Value Function
1\Input A).
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com