Fault Finding
7-1
512C Series Converter
F
AULT
F
INDING
Troubleshooting
PROBLEM
POSSIBLE CAUSE
REMEDY
No "Power On" LED 2
Illuminated
No Supply Available
Check Supply Availability and Supply Fuse fitted or
Circuit Breaker closed.
Incorrect Supply Voltage
Applied to Controller
Check Supply Voltage and Transformer Tapping
position are compatible.
Motor will not run at
Switch On
Start/Run Signal not present
Check Control Circuit Wiring
No Speed Setpoint
Check Total Setpoint terminal 12. Check Setpoint
Potentiometer & Wiring
No Armature Current
Check P4 adjustment & External Current Limit
Potentiometer setting & wiring (if used)
No Field
Check Field AC Supply and Field connections
Motor Jammed
Free Obstruction
Motor Runs and Stops
after short
Incorrect Current Limit Setting Check P4 setting
Check external current limit setting
period with "Stall" LED1
Illuminated
Incorrect Current Calibration Check Programming Switches SW5,6,7
Motor Jammed
Free Obstruction
Incorrect Feedback Voltage
Calibration
Check Feedback Voltage Calibration Switches SW1/2.
Note These Switches must be set for both
Tachogenerator & Armature Voltage Feedback
Maximum Controller Output
Exceeded
Check compatibility of Motor Voltage to Controller
Output Voltage
Faulty Tachogenerator and/or
Coupling.
Check Tachogenerator (use Armature Voltage
Feedback Temporarily)
Motor runs at Full Speed
only
Incorrect Tachogenerator
Polarity or Open Circuit
Tachogenerator
Check Tachogenerator viability and connectivity
Open Circuit Speed Setpoint
Potentiometer
Check Terminal 13 or 10 as appropriate
Minimum Speed Setting
Check Minimum Speed Potentiometer P6
Motor runs with Zero
Setpoint.
Zero Speed Offset Adjustment Adjust P8 to give Zero Speed
Motor Speed
Stability P3
Reduce P3
Oscillating
IR Compensation P5
No IR compensation for Tachogenerator Feedback.
Reduce P5 for Armature Voltage Feedback