background image

   English

1/4

    AS  D  10-100      

1 Safety

1.1  Importance of the manual

• Keep it for the entire life of the machine.
• Read it before any operation.
• It is subject to changes: for updated information see the version on 

the unit.

1.2 Warning signals

!

Instruction for avoiding danger to persons

Y

Instruction for avoiding damage to the equipment.

Z

The presence of a skilled or authorized technician is required.

,

Th

  ere are symbols whose meaning is given in the para. 8.1

1.3 Safety instructions

Every unit is equipped with an electric disconnecting switch for 

operating in safe conditions. Always use this device in order to eliminate 
risks maintenance.

!

 Th

  e manual is intended for the end-user, only for operations per-

formable with closed panels: operations requiring opening with tools 
must be carried out by skilled and qualifi ed personnel.

Y

 Do not exceed the design limits given on the data plate.

!Y

 

It is the user’s responsibility to avoid loads diff erent from the 

internal static pressure. Th

  e unit must be appropriately protected when-

ever risks of seismic phenomena exist.

Th

  e safety devices on the compressed air circuit must be provided 

for by the user
Th

  e dimensioning of the safety devices of the air compressed circuit 

must be according to the specifi cations of the system and legislation in 
force locally.
Only use the unit for professional work and for its intended purpose.
Th

  e user is responsible for analysing the application aspects for product 

installation, and following all the applicable industrial and safety stand-
ards and regulations contained in the product instruction manual or 
other documentation supplied with the unit.
Tampering or replacement of any parts by unauthorized personnel and/
or improper machine use exonerate the manufacturer from all responsi-
bility and invalidate the warranty. 
Th

  e manufacturer declines and present or future liability for damage to 

persons, things and the machine, due to negligence of the operators, 
non-compliance with all the instructions given in this manual, and non-
application of current regulations regarding safety of the system.

Th

  e manufacturer declines any liability for damage due to alterations 

and/or changes to the packing.
It is the responsibility of the user to ensure that the specifi cations pro-
vided for the selection of the unit or components and/or options are 
fully comprehensive for the correct or foreseeable use of the machine 
itself or its components.

!

IMPORTANT: Th

  e manufacturer reserves the right to modify this 

manual at any time. Th

  e most comprehensive and updated information, 

the user is advised to consult the manual supplied with the unit.

1.4 Residual risks

Th

  e installation, start up, stopping and maintenance of the machine 

must be performed in accordance with the information and instructions 
given in the technical documentation supplied and always in such a way 
to avoid the creation of a hazardous situation. 
Th

  e risks that it has not been possible to eliminate in the design stage are 

listed in the following table:

Part aff ected

Residual

risk

Manner of

exposure

Precautions

heat exchanger 
coil

small cuts

contact

avoid contact, wear protective 
gloves

fan grille and fan lesions

insertion of pointed 
objects through the 
grille while the fan is in 
operation

do not poke objects of any 
type through the fan grille or 
place any objects on the grille

inside the unit:
compressor and 
discharge pipe

burns

contact

avoid contact, wear protective 
gloves

inside the unit: 
metal parts and 
electrical wires

intoxication, 
electrical 
shock, serious 
burns

defects in the insulation 
of the power supply lines 
upstream of the electrical 
panel; live metal parts

adequate electrical protection 
of the power supply line; en-
sure metal parts are properly 
connected to earth

outside the unit: 
area surrounding 
the unit

intoxication, 
serious burns

fi re due to short circuit or 
overheating of the supply 
line upstream of the unit’s 
electrical panel

ensure conductor cross-
sectional areas and the supply 
line protection system con-
form to applicable regulations

8 Appendix

Th

  ere are symbols whose meaning is given in the par. 8.1.

8.1 Legend
8.2 Installation diagram
8.3 Technical data
8.4  Spare parts list
8.5 Exploded drawing
8.6 Dimensional drawings
8.7 Refrigerant circuit
8.8 Wiring diagram

Index

1 Safety

1.1  Importance of the manual
1.2 Warning signals
1.3 Safety instructions
1.4 Residual risks

2 Introduction

2.1 Transport
2.2 Handling
2.3 Inspection
2.4 Storage

3 Installation

3.1 Procedures
3.2 Operating space
3.3 Tips
3.4 Electrical connection
3.5  Condensate drain connection

4 Commissioning

4.1 Preliminary checks
4.2 Starting
4.3 Operation
4.4 Stop

5 Control

5.1  Option Free contact

6 Maintenance

6.1 General instructions
6.2 Refrigerant.
6.3  Preventive Maintenance Programme
6.4 Dismantling

7 Troubleshooting

Содержание ASD 10

Страница 1: ...DATE 24 02 2014 Rev 19 CODE 398H272867 ASD ASD 10 ASD 15 ASD 25 ASD 35 ASD 50 ASD 75 ASD 100 User manual Manuel d utilisation Manual de uso 60Hz Refrigeration Dryer...

Страница 2: ......

Страница 3: ...or components and or options are fully comprehensive for the correct or foreseeable use of the machine itself or its components IMPORTANT The manufacturer reserves the right to modify this manual at a...

Страница 4: ...ng distance 3 mm ahead of the system RCCB IDn 0 3A see the relevant current local regulations The nominal current In of the magnetic circuit breaker must be equal to the FLA with an intervention curve...

Страница 5: ...lourless gas classified in SAFETY GROUP A1 EN378 group 2 fluid according to Directive PED 97 23 EC GWP Global Warming Potential 1430 In case of refrigerant leakage ventilate the room 6 3 Preventive Ma...

Страница 6: ...eek external as sistance Ice formation on evapo rator low evaporation pressure By pass air flow keep ing air inlet open Open condensate drain valve manually Restart appliance checking setting of expan...

Страница 7: ...ications de l emballage L utilisateur doit s assurer que les conditions fournies pour la s lection de l unit ou de ses composants et ou options sont parfaitement conformes pour une utilisation correct...

Страница 8: ...thermique diff rentiel en amont de l installation RCCB IDn 0 3A avec une distance d ouverture des contacts 3 mm voir r glementation locale en vigueur en la mati re et s y conformer Le courant nominal...

Страница 9: ...males est un gaz incolore appartenant au SAFETY GROUP A1 EN378 fluide groupe 2 selon la directive PED 97 23 EC GWP Global Warming Potential 1430 En cas de fuite de r frig rant a rer le local 6 3 Progr...

Страница 10: ...re dans l vaporateur basse pres sion d vaporation by passer l air en maintenant ouverte l arriv e d air Ouvrir manuellement l vacuation des condensats Remettre en marche en v rifiant le tarage de la s...

Страница 11: ...s y o opciones sean exhaustivas para un uso correcto o razonablemente previsible de la misma unidad o de los componentes ATENCI N El fabricante se reserva el derecho de modificar sin previo aviso la i...

Страница 12: ...consulte las disposiciones locales al respecto La corriente nominal In de dicho magnetot rmico debe ser igual a FLA y la curva di intervenci n de tipo D 3 5 Conexi n del drenaje de condensados El sec...

Страница 13: ...EN378 fluido del grupo 2 seg n la directiva PED 97 23 EC GWP Global Warming Potential 1430 En caso de fuga de refrigerante airee el local 6 3 Programa de mantenimiento preventivo Per garantire nel tem...

Страница 14: ...icitar asistencia externa formaci n de hielo en el evaporador baja presi n de evaporaci n derivar el aire by pass dejando abierta la entrada de aire Abrir manualmente el drenaje de condensados Reactiv...

Страница 15: ...1 AS D 10 100 Appendice Ap ndice Appendix...

Страница 16: ...ie air de condensation Salida aire de condensaci n Condensation air outlet Entr e air de condensation Entrada aire de condensaci n Condensation air inlet 1 MC Compresseur Compresor Compressor 2 Conden...

Страница 17: ...eeding dryer design pressure Tuyaux flexibles pour raccordements de l air si le r seau est soumis des vibrations Tubos flexibles para las conexiones de aire si la red est expuesta a vibraciones Hoses...

Страница 18: ...llation lb Kg oz Kg In 115V 10 1ph 60Hz 230V 10 1ph 60Hz NPT N x m dB A 41 8 19 5 99 0 17 32 122 F 0 50 C 41 122 F 5 50 C 149 F 65 C 232 PSIg 16bar 3 74 3G16AWG NPT compatible 1 2 50 50 ASD 10 ASD 15...

Страница 19: ...85238 On request On request 398H785241 On request Spare parts Refrigerant condenser 2 398H114800 398H114801 398H144802 398H114803 398H114804 Evaporator Separator Air air heat exchanger 4 398H472157 39...

Страница 20: ...8 5 Exploded drawing 6 AS D 10 100 2 3 8 13 1 7 4 11 14 6 15 12 KA1 KT T01...

Страница 21: ...8 6 Dimensional ASD10 15 7 AS D 10 100 inches mm...

Страница 22: ...8 6 Dimensional ASD25 35 8 AS D 10 100 inches mm...

Страница 23: ...8 6 Dimensional ASD50 100 9 AS D 10 100 inches mm...

Страница 24: ...8 7 Refrigerant circuit ASD10 100 10 AS D 10 100...

Страница 25: ...8 8 Wiring diagram ASD10 15 11 AS D 10 100...

Страница 26: ...Wiring diagram ASD25 100 12 AS D 10 100...

Страница 27: ...Wiringdiagram optionalfreecontact ASD100 13 AS D 10 100...

Страница 28: ...e to adhere to this procedure will result in loss of warranty c Seller reserves the right to replace a product under warranty and will accept no costs as to the removal and installation of the product...

Страница 29: ...e de la garantie c La soci t fournisseur se r serve le droit de remplacer un produit sous garantie et n acceptera aucun frais de retrait et d installation des produits d La soci t fournisseur se r ser...

Страница 30: ...o y posteriormente enviado al Proveedor El incumplimiento de este procedimiento causar la invalidaci n de la garant a c El Proveedor se reserva el derecho a reemplazar un producto en garant a y no asu...

Страница 31: ...Information Centre Free phone 00 800 27 27 5374 from AT BE CH CZ DE DK EE ES FI FR IE IL IS IT LU MT NL NO PL PT RU SE SK UK ZA US Product Information Centre Toll free number 1 800 27 27 537 www park...

Страница 32: ...ifin Corporation Hiross Zander Division Zander Aufbereitungstechnik GmbH Im Teelbruch 118 45219 Essen Germany Tel 49 0 20 54 934 0 Fax 49 0 20 54 934 164 www Parker com A division of Parker Hannifin C...

Отзывы: