ControlNet Communications Interface - HA470733U001
3
Initial Power on Checks
With the correct connections to the
active PLC/SCADA supervisor, the
MODULE LED will be ON
continuously and the NETWORK
LED will flash to indicate the No
Connection State.
Understanding the LED Indications
Network and Module LED Indications
Network LED
Indicates the state of the
connected network.
Module LED
Indicates the set-up state of the LinkCard. The states
indicated are those produced by the FAULT parameter of
the LinkCard function block.
LED
Indication
Description
FAULT Parameter Description
OFF
Disabled
HARDWARE
Hardware Fault - external
FLASH
No Connection
CONFIGURING
Card is initializing
ON
Data exchange
NONE
Valid set-up, ready for external
communications
Figure 2. LED Status Indication
Note: The NETWORK LED is always in the OFF State when the MODULE LED is
not
ON continuously,
indicating that the LinkCard is not receiving external communications or the PLC is off.
ON
MODULE LED
FLASH
NETWORK
LED
Figure 3. ControlNet connections to the L5354
-L5354-
C
ontrol
N
et
™
NETWORK
STATUS
MODULE
STATUS