ControlNet Communications Interface - HA470733U001
12
Appendix A
Configuration Tips
1. Define the total amount of data you wish to send to and from the ControlNet scanner. The
limit for the card is 224 words each way. You can have less and the number of inputs and
outputs do not have to match. The LINK blocks are 8 words each. Your total words should
be a multiple of 8.
2. Inputs are words transmitted from the LINK module to the PLC. These will be LINK writer
blocks. Outputs are words transmitted from the PLC to the LINK module. These are LINK
reader blocks.
3. The LinkCard transmits two status words so the total number of input words will be your data
size plus two.
4. The ControlNet Node Address for the LinkCard is assigned using the DSD software. The
rotary switches on the LinkCard are set to 00.
5. The bottom coaxial connector is for the primary ControlNet network.
6. The minimum Network Update Time for the card is 5ms.