PGC, Inc.
Appendix B; SmartPad version 0.503
Steady State & Programmable
November 2005
B-28
PGC SmartPad™ Serial Communications
The SmartPad™ is capable of communication with a remote terminal via RS-232 protocol. The
connection is made at a DB-9 male connector on the cabinet.
I. OVERVIEW:
This section of the manual will explain the use and function of the communications feature. The
SmartPad™ is capable of communication with a remote terminal via RS-232 protocol. Through
this interface the user can modify the control set points or the tuning values. The user can also
request the current set points, tuning values, percentage output or the measured process
variables. This functionality will allow the user to collect performance data from the controller
or store test procedures on a remote terminal. These stored test procedures can then be
downloaded to the SmartPad™, giving the user unlimited programming capability.
A complimentary copy of SmartLog™ is available by request. SmartLog™ provides a Windows
based platform for data collection, chamber control and real-time graphing.
II. HARDWARE CONNECTIONS:
Connect the remote terminal to the nine pin header on the back of the SmartPad™ or DB-9 Male
connector on the cabinet. Maximum cable length should be limited to 50 feet with RS-232
protocol. The required connections are as follows.
Terminal
# Function
5
Common
2
Terminal Receive (data from SmartPad™)
3
Terminal Transmit (data to SmartPad™)
III. TERMINAL PROTOCOL:
Any terminal program or application that is capable of sending and receiving ASCII characters
should be capable of communicating with the SmartPad™. All hardware handshaking should be
disabled in the terminal since there are no hardware handshaking connections on the SmartPad™
connector. The command sample rate should also be limited to greater than 10 milliseconds
between request commands (?) and 20 mS. between input commands (=).
The protocol settings on the terminal should be:
Baud
rate:
9600
Parity:
None
Data
Bits:
8
Stop
Bits:
1
Soft flow control (XON/XOFF):
on
Hard flow control (RTS/CTS):
off
Carriage return translation:
none (CR = CR only)
Line feed translation:
strip (CR = CR only)
Line pacing (command frequency):
10 milliseconds or greater for requests, 20 mS or
greater for inputs.
Local character echo:
off
Duplex:
full
Carrier detection:
do not abort if CD is lost (no hardware handshaking)
Содержание 9354-4250
Страница 2: ...PGC Inc Horizontal 500 1000 CFM June 2006 Parameter Generation and Control Inc 2 ...
Страница 42: ...PGC Inc Appendix B SmartPad version 0 503 Steady State Programmable November 2005 B 1 ...
Страница 83: ......
Страница 84: ......
Страница 85: ......
Страница 86: ......
Страница 87: ......
Страница 88: ......
Страница 89: ......
Страница 90: ......