PGC, Inc.
Appendix B; SmartPad version 0.503
Steady State & Programmable
November 2005
B-31
INPUT COMMANDS:
(Note: Sign byte is optional on inputs. Set point input commands may only be used in steady state modes)
Command
Function
=OO
<CR>
Toggles current run state (
O
n/
O
ff command)
=RC
<CR>
Instructs Smart Pad to reboot in
R
h
C
ascade control mode
=TT
<CR>
Instructs Smart Pad to reboot in
T
wo
T
emperature control mode
=DY
<CR>
Instructs Smart Pad to reboot in
D
ryer control mode
=SD
<CR>
Instructs Smart Pad to reboot in
S
low
D
amper control mode
=SS
<CR>
Instructs Smart Pad to reboot in
S
teady
S
tate set point entry mode
=PG
<CR>
Instructs Smart Pad to reboot in
P
ro
g
rammable set point entry mode
=AS
<SP>xx.xx<CR>
Inputs xx.xx as the new
A
ir
S
et point
=AH
<SP>xx.xx<CR>
Inputs xx.xx as the new
A
ir
H
alf proportional band
=AR
<SP>xx.xx<CR>
Inputs xx.xx as the new
A
ir
R
eset rate
=AD
<SP>xxx<CR>
Inputs xxx as the new
A
ir
D
erivative constant
=XS
<SP>xx.xx<CR>
Inputs xx.xx as the new au
X
iliary
S
et point
=XH
<SP>xx.xx<CR>
Inputs xx.xx as the new au
X
iliary
H
alf proportional band
=XR
<SP>xx.xx<CR>
Inputs xx.xx as the new au
X
iliary
R
eset rate
=XD
<SP>xxx<CR>
Inputs xxx as the new au
X
iliary
D
erivative constant
The following command is available in Two Temperature mode only.
=WS
<SP>xx.xx<CR>
Inputs xx.xx as the new
W
ater
S
et point
=WR
<SP>xx.xx<CR>
Inputs xx.xx as the new
W
ater
R
eset rate
=WH
<SP>xx.xx<CR>
Inputs xx.xx as the new
W
ater
H
alf proportional band
=WD
<SP>xx.xx<CR>
Inputs xx.xx as the new
W
ater
D
erivative constant
The following commands are available in a Cascade mode only.
=WL
<SP>xx.x<CR>
Inputs xx.x as the new
W
ater
L
ower limit
=WU
<SP>xx.x<CR>
Inputs xx.x as the new
W
ater
U
pper limit
=RS
<SP>xx.xx<CR>
Inputs xx.xx as the new
R
h
S
et point
=RH
<SP>xx.xx<CR>
Inputs xx.xx as the new
R
h
H
alf proportional band
=RR
<SP>x.xxx<CR>
Inputs x.xxx as the new
R
h
R
eset rate
=
RD
<SP>xxx<CR>
Inputs xxx as the new
R
h
D
erivative constant
The following commands are available in Slow Damper mode only.
=DH
<SP>xx.xx<CR>
Inputs xx.xx as the new
D
amper
H
alf proportional band
=DR
<SP>x.xxx<CR>
Inputs x.xxx as the new
R
h
R
eset rate
The following commands are available in programmable modes only.
=GO
<CR>
Instructs the program to run/resume
=ST
<CR>
Instructs the program to halt
=LUP
<SP>xx<SP>yy<SP>zz<CR>
Inputs xx,yy,zz as the new loop (
LUP
) parameters [start seg; loop from seg;
loop to seg] This command will also reinitialize the loop at the new loop parameters.
=PR
<SP>xx<SP>aa.a<SP>ww.w<SP>hh:mm:ss<CR>
Inputs
the
PR
ogram data, air (aa.a) and water
(ww.w) set points and time (hh:mm:ss), for the segment indicated (xx).
=IN
<CR>
Instructs the program to re
IN
itialize the loop at the existing loop parameters.
Содержание 9354-4250
Страница 2: ...PGC Inc Horizontal 500 1000 CFM June 2006 Parameter Generation and Control Inc 2 ...
Страница 42: ...PGC Inc Appendix B SmartPad version 0 503 Steady State Programmable November 2005 B 1 ...
Страница 83: ......
Страница 84: ......
Страница 85: ......
Страница 86: ......
Страница 87: ......
Страница 88: ......
Страница 89: ......
Страница 90: ......