Model ERC2 – 131xxx, 151xxx, and 351xxx  

(Control Mechanism / Remote Display Module)

Figure. 5

Figure. 6

INsTALLATION INsTruCTIONs

 iMPORTANT

   All ERC-2 series controls are designed as operating controls only. if 

an operating control failure could result in personal injury or loss of 

property, a separate safety control and/or alarm should be installed.

•   The schematic drawings and other information included in this 

specification sheet are for the purpose of illustration and general 

reference only.

•   These instructions do not expand, reduce, modify or alter the 

Robertshaw Terms in any way; and no warranty or remedy in favor of 

the customer or any person arises out of these instructions.

•   The ERC-2 control has been certified by Underwriters Laboratories 

Inc. The certification does not extend to their use for any 

other purpose. Robertshaw assumes no responsibility for any 

unconventional application of its control unless such application has 

been approved in writing by Robertshaw.

•   It is the responsibility of the installer and the user to assure that his 

or its application and use of Robertshaw products are in compliance 

with all federal, state and local requirements, including, without 

limitation, all requirements imposed under the National Electric 

Code and any applicable building codes.

CAuTION

TO PREVENT POSSIbLE ELECTRIC SHOCk OR EqUIPMENT 

DAMAgE, DISCONNECT ELECTRICAL POwER TO THE UNIT 

bEFORE AND DURINg INSTALLATION. 

DO NOT

 RESTORE 

ELECTRICAL POwER TO THE UNIT UNTIL THE CONTROL IS 

PROPERLy INSTALLED AND THE CASE OR PANEL DOOR IS 

CLOSED. DO NOT LOCATE THE CONTROL IN AN ExPLOSIVE 

ATMOSPHERE AS A SAFETy HAzARD CAN RESULT DUE 

TO POSSIbLE SPARk gENERATION IN THE CONTROL. USE 

OF CONTROL IN SUCH  ENVIRONMENTS MAy RESULT 

IN INjURy OR DAMAgE OF THE PERSONS OR PROPERTy 

(OR bOTH) AND ARE LIkELy TO SHORTEN CONTROL LIFE. 

ROBERTShAw ASSUMES NO RESPONSiBiliTy FOR ANy 

SUCh USE.

Mount the ERC-2 to a wall or any flat surface using the three holes in 

the metal case (models ERC-2 - x11xxx and x21xxx) or the 4 holes in 

the plastic support for the ERC-2 - 131xxx, 151xxx, and 351xxx models. 

The control’s components are not position sensitive, but should be 

mounted so they can be easily wired and adjusted. The models that do 

not come in a metal case must be mounted inside an enclosure (NEMA 

1 type or better). Avoid excessive conditions of moisture, dirt, dust and 

any corrosive atmosphere.

Mounting Dimensions – Metal Case

Содержание ERC-2

Страница 1: ... the Clock It maintains the correct time of day for up to 100 hours Microprocessor Based Electronics High reliability and repeatability FCC Compliance This device complies with CFR 47 Part 15 Class A FCC requirements Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 This device must accept any interference received including interference th...

Страница 2: ...ation time amount of time for the defrost duration It also functions as a back up for temperature termination Defrost termination temperature temperature that will cause the defrost to terminate if reached before defrost duration time Fan start temperature temperature that will cause the fan to re start after defrost Setpoint Setpoint temperature cut out a setpoint temperature can be programmed to...

Страница 3: ...re in compliance with all federal state and local requirements including without limitation all requirements imposed under the National Electric Code and any applicable building codes CAUTION To prevent possible electric shock or equipment damage disconnect electrical power to the unit before and during installation DO NOT restore electrical power to the unit until the control is properly installe...

Страница 4: ...rsion 2 Connect the defrost device heater or hot gas solenoid to the terminal in the control Figs 10 and 11 3 Connect the wire from L1 120V AC or 208 240V AC line to the terminal marked as COM 4 Connect also the fan wires to the terminals marked as FAN 5 Use the alarm connections to connect an alarm to the control as shown in Figures 10 and 11 Figure 10 Load AC Input Connectors Quick Connects Figu...

Страница 5: ...displayed Step 4 Press SET to accept the new time Step 5 Press DOWN to go to the next parameter Setpoint Temperature SEt cut out Step 6 Press SET to change the setpoint temperature Step 7 or Press UP or DOWN to go to the desired setpoint The range is 40 to 60 F or 40 to 16 C Step 8 Press SET to accept the change Step 9 Press DOWN to exit the first level of programming Note 1 During programming if ...

Страница 6: ...from 0 to 59 minutes Compressor Run Time CPrn Time the compressor will run between defrosts Number of Defrosts nodF Number of defrosts per day from 0 to 8 0 means 1 defrost every 48 hours Defrost Start Time dEF1 8 Start time of each defrost Defrost Duration dEFd Defrost duration time back up for defrost termination temperature Range from 0 minutes to 4 hours Fan Delay FAnd Delay time for the fan a...

Страница 7: ...rature Alarm indicates that the temperature has gone above the high alarm setpoint For Error Codes 1 and 2 cut the power to the unit and correct the problem to reset the display For Codes 3 and 4 press the UP or DOWN button on the display to reset the error message If the display still shows the message the sensor must be replaced The Error Codes 6 and 7 will be automatically reset once the temper...

Страница 8: ... Ranco Paragon and Uni Line are trademarks of Robertshaw its subsidiaries and or affiliated companies All other brands mentioned may be the trademarks of their respective owners For Technical Service Telephone 1 800 445 8299 TechnicalService robertshaw com www uni line com www robertshaw com 2015 Robertshaw 10 15 7515010 Rev E 8 ...

Отзывы: