6 Complete Installation Manual
3.2
FIRE ZONE PROGRAMMING
Section [20] option [4]
When option
[4]
is disabled, the control panel will recognize the zone as a 24Hr. Burglary Zone (see section 3.1.4). When option
[4]
is enabled,
the control panel will recognize zone 6 as a
Fire Zone
, enabling smoke detectors connected as shown in Figure 8-2: Zone Connections on page
14. Fire zones must use a 1k
Ω
EOL resistor. If there is a line short or if the smoke detector becomes active, whether the system is armed or
disarmed, the control panel will generate an alarm. Alarms are always audible, regardless of other settings. Fire alarms will generate an
intermittent (pulsed) bell/siren output signal as demonstrated in
Figure 3-1: Bell Output during Fire Alarm
.
Option
[4]
OFF
:
Zone 6 is a 24Hr. Burglary Zone (default)
Option
[4]
ON
:
Zone 6 is a Fire Zone
Figure 3-1: Bell Output during Fire Alarm
3.3
ZONE SPEED
Section [19] option [1]
The Zone Speed defines how quickly the control panel will respond to an open zone. The control panel will not display an open zone on the
keypad or generate an alarm until the programmed Zone Speed has elapsed. All other zone definitions and options do not come into effect until
the Zone Speed has elapsed. This feature prevents any momentary glitches from causing an alarm.
Option
[1]
OFF
:
Zone Speed is 600ms (slow) (default)
Option
[1]
ON
:
Zone Speed is 20ms (fast)
It is recommended to avoid using option
[1]
ON for Keypad Zones
.
4:
SYSTEM OPTIONS
4.1
EXIT DELAY TIMER
Section [10]
After entering the required arming sequence (i.e. User Access code), the Exit Delay Timer determines the amount of time a user has to leave the
protected area before the control panel arms the system. The Exit Delay applies to all zones in the system. The keypad will beep rapidly and the
READY
LED will flash during the Exit Delay. Key in the desired two-digit value from 00 to 99 seconds into section
[10]
(30 seconds by default).
4.2
ENTRY DELAY TIMER
Section [11]
When the system is armed and a zone defined with the Entry Delay Option opens (see section 3.1), the control panel will generate an alarm after
the programmed Entry Delay Timer has elapsed if the system is not disarmed. This is to provide users with enough time to enter the protected
area and disarm the system. To program the Entry Delay Timer, key in the desired 2-digit delay value (00 to 99 seconds) into section
[11]
(45
seconds by default). Entry Delay zones are commonly used at the entry/exit points of the protected area (i.e. front/back door, garage, etc.).
4.3
BELL CUT-OFF TIMER
Section [12]
After an audible alarm, the bell/siren output will deactivate when the system is disarmed or when the Bell Cut-off Timer has elapsed, whichever
comes first. Key in the desired two-digit value from 00 to 99 minutes into section
[12]
(04 minutes by default).
4.4
PANIC ALARM
Section [19] option [6]
In case of emergency, the
Spectra 1727
system provides one panic alarm. This panic alarm, if enabled, will immediately generate an alarm after
pressing and holding the
[1]
and
[3]
keys for two seconds. In the Alarm Memory (see section 6.8) the
[8]
key will illuminate to indicate that
someone activated the Panic Alarm.
Option
[6]
OFF
:
Panic Alarm is disabled (default)
Option
[6]
ON
:
Panic Alarm is enabled
4.5
ARMING OPTIONS
4.5.1
A
UTO
F
ORCE
A
RMING
Section [19] option [7]
With this feature enabled, the control panel will always Force arm instead of Regular arm regardless of the User Access Code’s programming. In
installations where the user must Force arm when leaving the protected area, this feature allows users to Force arm without pressing the
[
FORCE
]
key before entering their User Access Code.
Option
[7]
OFF
:
Auto Force Arming is disabled (default)
Option
[7]
ON
:
Auto Force Arming is enabled
Содержание SPECTRA 1686H
Страница 1: ...SPECTRA 1727 V1 10 1727 COMPLETE INSTALLATION MANUAL Reference Installation and Programming...
Страница 2: ......
Страница 15: ...Spectra 1727 13 8 HARDWARE CONNECTIONS Figure 8 1 PCB Layout...
Страница 16: ...14 Complete Installation Manual Figure 8 2 Zone Connections Figure 8 3 PGM Connections...
Страница 18: ...16 Complete Installation Manual Notes...
Страница 19: ......
Страница 20: ......