EVOHD+ Installation Guide
Alarm Options
Bell/alarm Output
(default =
only option [1] enabled
) When an alarm condition is detected in a partition, the control panel can trigger the on-board
BELL
output enabling any bells or
sirens connected to it. In section
[3032]
enable the option to enable the bell output in the desired partition (off = disabled):
Bell Cut-off Timer
(default =
004
) After an audible alarm, the bell or siren will stop once the partition is disarmed or when the Bell Cut-Off Timer has elapsed. Enter any value between
001 and 255 minutes:
No Bell Cut-Off on Fire Alarm
S
ECTION
[3030]: O
PTION
[2]
(default =
disabled
) The control panel can disable the Bell Cut-Off Timers when alarms are generated from zones defined as Standard or Delayed Fire Zones (see
BELL
output will remain enabled until a user disarms the partition in alarm.
Recycle Alarm Rate
(default =
000
) The control panel re-verifies the zone status during an alarm at a programmed rate once the Bell Cut-Off Timer and the Recycle Delay elapse. If open
zones remain, the control panel will regenerate the alarm. Enter the number of times from 001 to 255 (000 = no limit) in one armed period that the control panel will
re-verify the zone status:
Recycle Delay
(default =
000
) The Recycle Delay is the amount of time the control panel will wait after the Bell Cut-off occurs before re-verifying the zone status. Program the
Recycle Delay from 001 to 255 minutes (000 = disabled):
Wireless Transmitter Supervision Options
S
ECTION
[3034]: O
PTIONS
[1]
AND
[2]
When the control panel detects a Supervision Loss, the control panel can generate an alarm and/or trouble, unless the Wireless Transmitter Supervision Option is
disabled.
Supervision Bypass Options
S
ECTION
[3034]: O
PTION
[3]
(default =
disabled
) When enabled in section
[3034]
, the Wireless Transmitter Supervision Options will follow the zone's bypass definition. The control panel will not
perform any action if a supervision loss occurs on a bypassed zone. When disabled, it will ignore the bypass definition and will follow the option set in section .
Partition 1: Option
[1]
Partition 5: Option
[5]
Partition 2: Option
[2]
Partition 6: Option
[6]
Partition 3: Option
[3]
Partition 7: Option
[7]
Partition 4: Option
[4]
Partition 8: Option
[8]
Partition 1:
[3113]
Partition 3:
[3313]
Partition 5:
[3513]
Partition 7:
[3713]
Partition 2:
[3213]
Partition 4:
[3413]
Partition 6:
[3613]
Partition 8:
[3813]
Partition 1:
[3117]
Partition 3:
[3317]
Partition 5:
[3517]
Partition 7:
[3717]
Partition 2:
[3217]
Partition 4:
[3417]
Partition 6:
[3617]
Partition 8:
[3817]
Partition 1:
[3116]
Partition 3:
[3316]
Partition 5:
[3516]
Partition 7:
[3716]
Partition 2:
[3216]
Partition 4:
[3416]
Partition 6:
[3616]
Partition 8:
[3816]
[1] [2]
Description
OFF OFF
Disabled (default):
Displays zone open on the keypads, therefore will generate an alarm when the system is armed.
Not permitted on UL systems.
OFF ON
Generates Trouble Only (when armed or disarmed):
The control panel displays
Zone Fault
in the Trouble Display and transmits the defined report
ON OFF
When disarmed: Generates Trouble Only
The control panel displays
Zone Fault
in the Trouble Display and transmits the defined report
code (see
When armed: Follows Zone Alarm Type
The control panel follows the zone’s alarm type (see
ON
ON
When disarmed: Generates Audible Alarm
The control panel displays
Zone Fault
in the Trouble Display, transmits the defined report code
on page 40), and generates an audible alarm.
When armed: Follows Zone Alarm Type
The control panel follows the zone’s alarm type (see