9
Section 5 Installation
5.1 Introduction
This section contains unpacking, inspection, installation instructions and
recommendations for the MAF 900-60S MCPA. It is important that the operator perform
the following tasks correctly and in good faith.
1. Carefully read all materials in this section prior to equipment unpacking or
installation.
2. Also read and review the operating instructions in Section 4 prior to installing the
amplifier.
3. If applicable, carefully review the Federal Communications Commission (FCC)
rules and regulation as they apply to your installation
5.2 Site Survey
Paradigm Wireless Systems recommends that a qualified individual or firms prior to
equipment ordering or installation perform a site survey. Performing a survey will reduce
or eliminate installation and turn-up delays caused by oversights. Attentions to power
plant capacity, battery back up, cooling/air conditioning, AC breakers capacity, RF/DC
cabling/breaker requirements are essential.
5.3 Electrical Service Recommendations
Paradigm Wireless Systems recommends that:
•
Proper AC line conditioning and surge suppression be provided on the primary AC
input to the +27 Vdc source.
•
All electrical service should be installed in accordance with the National Electrical
Code, any applicable state or local codes, and good engineering practice.
•
Grounding of all equipment should be in accordance to Bellcore standards.
•
Circuit breakers should be thermal type, capable of handling the anticipated inrush
current.
5.4 Air Conditioning
Each MAF 900-60S MCPA will generate approximately 1900 BTU of heat. When using
more than one amplifier it is recommended that a thermal analysis be performed.
Ensuring proper cooling will extend the Mean Time Before Failure of the unit.
5.5 Unpacking and Inspection
This equipment (as applicable) has been operated, tested, and calibrated at the factory.
Carefully open and remove the MAF 900-60S amplifier from the shipping container.
Retain all packing material and shipping container in the event that the unit must be
returned to the factory. Please perform the following steps: