AVT System Cable Removal 

 

 

 

 

 

1.

 

Grip the Retention Spring on both 

sides.  

 

2.

 

Pull down on the Retention Spring 

approximately 

1/16 inch [1.5 mm]. 

3.

 

Continue holding the Retention Spring 

down while pulling back on the right-angle 

connector to release the AVT System Cable. 

 

O-ring Replacement  

 

 

Cap closure O-ring 

Sealing O-ring 

The O-rings can be replaced if they become dry or brittle. In critical sealing applications, such as wash down environments, it 

is recommended that the O-rings be replaced every 5 years. Apply a light coating of silicone grease to the O-rings to promote 

sealing and extend O

-ring life. 

 

Cleaning Instructions 

The Indicator Module can be cleaned with a damp cloth or isopropyl alcohol based cleaner. Do not use abrasives or high 

alkaline cleaners. Do not leave cleaners on the device for a long period, rinse immediately. Do not apply cleaners in direct 

sunlight or elevated temperatures. 

 

The section of the VeriSafe Indicator Module that is external to the electrical enclosure is approved for 

wash down as specified 

by NEMA 4 and IP66 standards. Before a wash down operation, ensure the O-rings are in good condition, the faceplate is not 

damaged and fully secured to the unit, and the cap is fully installed. 

 

Visual Inspection 

Periodically inspect the AVT and replace any damaged parts, cables or terminations. 
Inspect the Sensor Lead terminations to ensure they are tight, the leads are secure and do not show signs of damage.  
Inspect the AVT System Cable to ensure it is locked into place on both ends, is secure and does not show signs of damage. 
Inspect the Indicator Module to ensure O-rings are not dry or brittle and that the retaining nut and cap are in place. 
The procedure described in the Commissioning Checklist can be performed at any time. 

Содержание VS-AVT-C02-L10

Страница 1: ...echsupport panduit com Tel 1 866 405 6654 EU Tech Support emeatoolservicecenter panduit com Tel 31 546 580 452 Fax 31 546 580 441 www panduit com Asia Pacific Tech Support TechSupportAP panduit com Te...

Страница 2: ...ts 4 Output Contacts 4 Technical Specifications 5 Dimensions 7 Schematics 8 Installation Considerations 11 Installation Instructions 13 Commissioning Checklist 15 Operating Instructions 16 Troubleshoo...

Страница 3: ...e shown in the Maintenance section of this instruction manual The product uses a lithium battery that is a fire explosion and severe burn hazard Do not crush recharge disassemble or heat above 85 C in...

Страница 4: ...es dans le tableau indiqu dans la section Maintenance de ce mode d emploi Le produit utilise une batterie au lithium qui est un incendie une explosion et un grave risque de br lure Ne pas craser recha...

Страница 5: ...hen the green Absence of Voltage Indicator is illuminated By wiring to these contacts the AVT can be used as an input to a control system as well as log when the absence of voltage was verified Recomm...

Страница 6: ...nce characteristics Limits and methods of measurement IEC EN61000 3 2 IEC EN61000 3 3 Electromagnetic compatibility EMC Part 3 2 Limits Limits for harmonic current emissions equipment input current 16...

Страница 7: ...ree 3 Altitude Up to 2000 meters 1 24 miles Battery Type Industrial 3 6V Lithium AA see table in Maintenance section for list of compatible batteries Functional Safety Mode of operation Continuous Hig...

Страница 8: ...4 2018 Dimensions Isolation Module Indicator Module Panel Knockout Units inches mm The Indicator Module is designed for use with a standard 30 mm knockout with notch The notch should be positioned on...

Страница 9: ...y or death Sensor leads of the same color should be terminated on the same conductor Each conductor should have at least one sensor lead set as shown on the schematic diagrams If a Sensor Lead separat...

Страница 10: ...MANUAL VeriSafe AVT B21052_05 Page 9 of 20 4 2018 Single Phase 2 Wire PE Single Phase 2 Wire PE Redundant Detection Lead Single Phase 3 Wire PE Corner Grounded DELTA 3 Wire PE High Leg DELTA 3 Wire N...

Страница 11: ...Panduit Corp 2018 INSTRUCTION MANUAL VeriSafe AVT B21052_05 Page 10 of 20 4 2018 DC System 2 Wire PE Redundant Detection Lead...

Страница 12: ...AVT is suitable for use on circuits delivering up to 300 000 rms symmetrical A at 600 V Use of Overcurrent Protection Installation of an AVT with overcurrent protection is neither required nor recomme...

Страница 13: ...pass This would be a multi fault scenario but is possible if terminations are not made properly and secured An AVT installed on a single phase system might only have one Detection Lead terminated to...

Страница 14: ...false absence of voltage indication Ensure that all sensor leads are terminated properly and secured to the power conductor or other nearby rigid feature to prevent movement if the termination fails t...

Страница 15: ...r leads with a splice Use approved connection methods and follow local codes and standards when terminating the sensor leads Secure the sensor leads to the conductors to prevent the leads from contact...

Страница 16: ...el Verify that the label is placed near the isolation module and marked to indicate where the AVT is installed Record changes to panel documentation Close panel and secure doors covers Press the Test...

Страница 17: ...f voltage push the Test Button A B Absence of Voltage Test Each time the Test Button is engaged the absence of voltage test sequence will be activated The test sequence includes running a self check u...

Страница 18: ...test 2 Voltage detected above the threshold Warning This indicates that the enclosure is energized Follow safety procedures and use the appropriate PPE when investigating the source of voltage If pane...

Страница 19: ...batteries approved for use with the AVT Do not discard the battery in the trash take it to an appropriate battery recycling facility Manufacturer Model Number Size Description Tadiran TL 5903 AA ER14...

Страница 20: ...h alkaline cleaners Do not leave cleaners on the device for a long period rinse immediately Do not apply cleaners in direct sunlight or elevated temperatures The section of the VeriSafe Indicator Modu...

Страница 21: ...to Buyer whichever is longer 4 No Warranty for Third Party Products Panduit makes no representations and disclaims all warranties of any kind express or implied relative to any third party product or...

Отзывы: