4-2018 

Commissioning Checklist:

 

 

Visually inspect the AVT:  

o

 

AVT system cable

:  Verify cable is locked into place on both the Indicator Module and 

Isolation Module. 

o

 

Indicator module

: Ensure o-ring is in place. Check that retaining nut is secure. Verify 

battery is installed and battery cap is locked into place. 

o

 

Isolation module

: Ensure module is secured to subpanel or DIN rail.  

o

 

Sensor leads

:  Gently pull on each Sensor Lead to ensure termination is secure. Verify 

that the Sensor Leads are secured to the power conductors or other nearby rigid feature 

to prevent movement and contact with a ground if the termination fails to remain 

intact.  Verify 

no wiring is exposed and all terminations are properly insulated

. Verify 

panel is clean and wiring debris is removed from panel. Verify that leads are connected 

as described in the appropriate wiring diagram from the Schematics section, including 

verifying that each conductor has two lead wires of matching color attached. Verify 

leads on each phase are not mechanically connected to each other.   

o

 

Instruction label

: Verify that the label is placed near the isolation module and marked 

to indicate where the AVT is installed.  

 

Record changes to panel documentation. 

 

Close panel and secure doors/covers. 

 

Press the Test Button to initiate the test. The yellow Caution Indicator should flash rapidly to 

indicate the test is in progress followed by the Absence of Voltage Indicator illuminated green.  

 

Review the Operating Instructions section of this manual before proceeding. 

 

 

Warning

:

  Always follow your company’s safety procedures when energizing equipment.  To avoid 

electric shock, use proper personal protective equipment when working on or near electrical hazards. 

 

 

Energize the system being monitored by the AVT. 

 

Verify that the red Voltage Presence Indicators are illuminated. 

 

Press the Test Button on the Indicator Module to initiate the absence of voltage test. 

 

Look for the yellow Caution Indicator to flash repeatedly before turning to a solid indication. 

**You should not see the green indicator illuminate when power is energized.** 

 

De-energize the circuit that is being monitored by the AVT.  

 

Verify that Voltage Presence Indicators are not illuminated. 

 

Press the Test Button on the AVT Indicator Module to begin the absence of voltage test. Look for 

the yellow Caution Indicator to flash and then the green Absence of Voltage Indicator should 

illuminate. 

 

 

Содержание VS-AVT-C02-L10

Страница 1: ...echsupport panduit com Tel 1 866 405 6654 EU Tech Support emeatoolservicecenter panduit com Tel 31 546 580 452 Fax 31 546 580 441 www panduit com Asia Pacific Tech Support TechSupportAP panduit com Te...

Страница 2: ...ts 4 Output Contacts 4 Technical Specifications 5 Dimensions 7 Schematics 8 Installation Considerations 11 Installation Instructions 13 Commissioning Checklist 15 Operating Instructions 16 Troubleshoo...

Страница 3: ...e shown in the Maintenance section of this instruction manual The product uses a lithium battery that is a fire explosion and severe burn hazard Do not crush recharge disassemble or heat above 85 C in...

Страница 4: ...es dans le tableau indiqu dans la section Maintenance de ce mode d emploi Le produit utilise une batterie au lithium qui est un incendie une explosion et un grave risque de br lure Ne pas craser recha...

Страница 5: ...hen the green Absence of Voltage Indicator is illuminated By wiring to these contacts the AVT can be used as an input to a control system as well as log when the absence of voltage was verified Recomm...

Страница 6: ...nce characteristics Limits and methods of measurement IEC EN61000 3 2 IEC EN61000 3 3 Electromagnetic compatibility EMC Part 3 2 Limits Limits for harmonic current emissions equipment input current 16...

Страница 7: ...ree 3 Altitude Up to 2000 meters 1 24 miles Battery Type Industrial 3 6V Lithium AA see table in Maintenance section for list of compatible batteries Functional Safety Mode of operation Continuous Hig...

Страница 8: ...4 2018 Dimensions Isolation Module Indicator Module Panel Knockout Units inches mm The Indicator Module is designed for use with a standard 30 mm knockout with notch The notch should be positioned on...

Страница 9: ...y or death Sensor leads of the same color should be terminated on the same conductor Each conductor should have at least one sensor lead set as shown on the schematic diagrams If a Sensor Lead separat...

Страница 10: ...MANUAL VeriSafe AVT B21052_05 Page 9 of 20 4 2018 Single Phase 2 Wire PE Single Phase 2 Wire PE Redundant Detection Lead Single Phase 3 Wire PE Corner Grounded DELTA 3 Wire PE High Leg DELTA 3 Wire N...

Страница 11: ...Panduit Corp 2018 INSTRUCTION MANUAL VeriSafe AVT B21052_05 Page 10 of 20 4 2018 DC System 2 Wire PE Redundant Detection Lead...

Страница 12: ...AVT is suitable for use on circuits delivering up to 300 000 rms symmetrical A at 600 V Use of Overcurrent Protection Installation of an AVT with overcurrent protection is neither required nor recomme...

Страница 13: ...pass This would be a multi fault scenario but is possible if terminations are not made properly and secured An AVT installed on a single phase system might only have one Detection Lead terminated to...

Страница 14: ...false absence of voltage indication Ensure that all sensor leads are terminated properly and secured to the power conductor or other nearby rigid feature to prevent movement if the termination fails t...

Страница 15: ...r leads with a splice Use approved connection methods and follow local codes and standards when terminating the sensor leads Secure the sensor leads to the conductors to prevent the leads from contact...

Страница 16: ...el Verify that the label is placed near the isolation module and marked to indicate where the AVT is installed Record changes to panel documentation Close panel and secure doors covers Press the Test...

Страница 17: ...f voltage push the Test Button A B Absence of Voltage Test Each time the Test Button is engaged the absence of voltage test sequence will be activated The test sequence includes running a self check u...

Страница 18: ...test 2 Voltage detected above the threshold Warning This indicates that the enclosure is energized Follow safety procedures and use the appropriate PPE when investigating the source of voltage If pane...

Страница 19: ...batteries approved for use with the AVT Do not discard the battery in the trash take it to an appropriate battery recycling facility Manufacturer Model Number Size Description Tadiran TL 5903 AA ER14...

Страница 20: ...h alkaline cleaners Do not leave cleaners on the device for a long period rinse immediately Do not apply cleaners in direct sunlight or elevated temperatures The section of the VeriSafe Indicator Modu...

Страница 21: ...to Buyer whichever is longer 4 No Warranty for Third Party Products Panduit makes no representations and disclaims all warranties of any kind express or implied relative to any third party product or...

Отзывы: