Troubleshooting
Warning
:
•
Always de-energize power before accessing an electrical enclosure.
•
Always follow safety and lockout/tagout procedures when working on or near electrical systems and equipment.
•
Use proper
personal protective equipment (PPE) when working around sources of hazardous electrical energy.
•
Battery, AVT System Cable and O-rings can be replaced. No other part of the product is serviceable. Do not
attempt to open the Indicator Module or Isolation Module for repair or modification. When servicing this product,
only use specified replacement parts.
The AVT checks for proper connection of the sensor and ground leads, verifies the battery voltage level is acceptable for proper
operation and verifies that the tester is working properly with a series of self checks. If it fails any of these tests, it will indicate
a failed test by illuminating the Caution Indicator for approximately 5 seconds. The AVT includes functionality to diagnose and
communicate the reasons for test failure with flashing of the Caution Indicator. If the test fails, illumination of the Caution
Indicator will be followed by a number of brief flashes ranging from 1-7. The number of flashes can be used to determine why
the absence of voltage test failed.
Number of
Flashes
Description
Recommended Actions
1
Battery voltage too low to run the test Replace the battery and re-test.
2
Voltage detected above the threshold
Warning: This indicates that the enclosure is energized.
Follow safety procedures and use the appropriate PPE
when investigating the source of voltage.
If panel has a stored energy source, wait several minutes
then re-test to see if energy has dissipated.
4
Proper installation of the sensor leads
could not be verified
Warning: The enclosure may be energized.
Follow safety procedures and use the appropriate PPE
when verifying the enclosure is de-energized before
performing additional troubleshooting.
Refer to the Installation Instruction section and verify that
the sensor leads are installed properly and that the device
is grounded properly.
3, 5, 6, or 7
Hardware failure
Contact Panduit Technical Support for additional
troubleshooting.
If the Caution Indicator does not illuminate after pressing the Test Button:
1.
Verify that the battery tray is fully engaged in the housing with the cap installed.
2.
Replace the battery. If the battery voltage is too low, the Indicator Module will not operate.
3.
Verify that the AVT System Cable is fully engaged in the connectors on the Indicator and Isolation Modules. The
Indicator Module will not function if it is not connected to the Isolation Module.
Should a problem occur during installation, operation or maintenance of the VeriSafe AVT, contact Panduit using
one of the technical support or customer service numbers listed on the cover of this manual. Contact Panduit if
you have any product problems related to the safety function of the product. The product model number and
serial number are printed on the Isolation Module and Indicator Module labels.