September 2022 9
VeriSafe Network Module User Guide, B21176 rev 1 [English]
ABOUT AVT
Displays firmware version, model number and universal identifier (UID) of the AVT . Use the refresh button to
update the card .
Refresh
AVT Data
ACTIVE FAULTS
This card will display active faults in the network module . The fault information is updated automatically every
3 seconds . See Troubleshooting for additional information .
21.
Faults
ID
Description
0
Hardware Failure . Flash code 2 during boot up
1
Power from the network module to the AVT is over the limit .
2
Indicate the network module has been reset to factory defaults
3
Data received from AVT was unable to be processed
4
Timeout while communicating with AVT
5
General SD card error
6
SD card is full
7
Time has not updated
8
Time not set
9
Web server could not load custom certificate
22.
Clear Faults
The Clear Faults button allows the user to clear any faults on the network
module . If the fault condition is still present the fault may be presented
after some time .