DOC#: T-PMPI-322EN
Page
3
of
4
Rev 02 [10-2018]
Step-by-Step Installation Procedure (continued from page 2 of 4)
6. See FIGURE 3 and FIGURE 4: Inspect location of factory-tightened TERMINAL in each TAP WIRE port
in connector.
•
Connector was shipped with each TERMINAL SCREW and TERMINAL in a factory-tightened state.
•
In a factory-tightened state, the TERMINAL blocks access to and restricts insertion of TAP WIRE.
•
Installer must loosen TERMINAL SCREW and push down on SCREW to ensure TERMINAL position
permits insertion of TAP WIRE.
•
REMOVE TAP TORQUE reminder label before proceeding to STEP 7.
7. See FIGURE 5: Loosen TERMINAL SCREW two turns and push down on SCREW to move TERMINAL.
•
Verify position of TERMINAL and repeat loosening two turns and repeat push down on the SCREW.
•
Repeat until TERMINAL is in the position shown in FIGURE 6. DO NOT completely loosen screw.
8. See FIGURE 6: Verify that TERMINAL is positioned at the bottom of port for TAP WIRE insertion.
•
TERMINAL must be positioned at bottom of port, permitting full-insertion of TAP WIRE.
COMPLETELY REMOVE
TAP TORQUE LABEL
FROM CONNECTOR
BEFORE STEP 7
TERMINAL
POSITION
RESTRICTS
INSERTION
OF TAP WIRE
FIGURE 3: TERMINAL POSITION
FIGURE 4: DETAIL VIEW
TERMINAL
OPENING IS VISIBLE WHEN
POSITIONED AT THE BOTTOM OF
THE WIRE PORT AND PERMITS
FULL-INSERTION OF THE TAP WIRE
Top Housing outline
shown for clarity of the
Terminal position
within the Connector
LOOSEN SCREW WITH T10 TORX
TORQUE-DRIVER AND
PUSH DOWN
ON SCREW HEAD
FIGURE 5: LOOSEN TERMINAL SCREWS AND
PUSH TERMINAL INTO PROPER POSITION
FIGURE 6: VERIFY TERMINALS ARE IN
PROPER POSITION AND
THAT TAP WIRE CAN BE
FULLY-INSERTED