INTELLIGENT NMC USER MANUAL
78
the NMC with the following settings.
Upload Certificate
Certificates ensure that in a secure connection, the user is authorized to access the
device. It is recommended that X.509 SSL certificate is uploaded the to the NMC and
that the certificate use a RSA 2048-bit key. The HTTPS Certificate and HTTPS Private
Key can be accessed from
Settings
→ Network settings → Web Access
Configuration
Figure 76: SSL Certificate Load Screen
Use SNMPv3c
The Panduit UPS NMC comes with support for both SNMPv2c and SNMPv3. For a
higher security deployment, it is recommended to disable SNMPv2c. Another
recommendation is to configure all SNMPv3 user and traps rece
iver with an “Auth Priv”
security level, authentication algorithm of SHA and a privacy algorithm of AES256.
Disabling unused interfaces
The default setting is to have HTTPS and SSH enabled. If these interfaces are not in
use, it is recommended to disable these interfaces.
Unused p
hysical ports may be protected using “lock out” plugs.