SMARTZONE UPS USER MANUAL
44
operations used to get to this page.
Status Information Page
These one to three pages provide the status of various miscellaneous points internal in
the UPS.
5-10kVA Single-phase UPS Units
The 5-10kVA single-phase UPS units have a single Status Info page.
Figure 23: Status Information Page (Single-Phase UPS)
This page contains the measured positive and negative bus voltage internal in the UPS
and the measured ambient temperature at the input of the UPS. The normal range of
this DC bus is between 280V to 470V. If the bus voltage is outside of this range, an
internal fault alarm will be triggered.
Press the up and over arrow to return to the Status Menu page. You can only get to this
page from the Status Menu page.
10-20kVA 3-Phase UPS Units
The 10-20kVA 3-phase UPS units have three Status Info pages.