For Technical Support: www.panduit.com/resources/install_maintain.asp
INSTRUCTIONS CM396F
A
B
C
D
Page 2 of 4
Step 3
Hinging Side Assembly on the two fasteners affixed in Step 2, rotate Side
Assembly upwards to align mounting holes in the two top brackets. Install
remaining (6) 3/8” Bolts and paint piercing washers in the locations shown
below. Stand the rack upright. Verify #12-24 tapped holes or Cage nuts are EIA
spaced at 18.31”. Square the rack by measuring the distance from A to D, and
B to C shown in 3.2. The difference in distance from A to D, and B to C should
be no greater than 1/8”.
Completely tighten all bolts to at least
14 ft.-lbs(19.0 N-m)
3.1
3.2
Grounding
Two hole ground lug attachment located on the top and
bottom rails of the side channel assembly at the loca-
tions shown. Remove masking before installing.
Grounding Locations
42.00"
30.21"
23.25"
39.50"
Turned
Out
16.00"
20.70"
Turned
In
[32.50"]
Turned
Out
[13.70"]
Turned
In
{45.5”}
Turned
Out
*51.0”*
Turned
Out
{26.7”}
Turned
In
*32.2”*
Turned
In
Mount rack to floor using the location guide below for mounting
hole and overall size information.
Location Guide
Note:
Floor Mounting Bolts must be used in all applications in order to
provide maximum rigidity, load bearing capacity and safety.The maximum
weight load is 2500 pounds. The weight load should be distributed evenly
across the height of the rack, with the heaviest components mounted at
the bottom of the rack.
X.XX
are dimensions for 30” deep 4 post racks
[x.xx] are dimensions for 23” deep 4 post racks
{x.xx} are dimensions for 36” deep 4 post racks
*x.xx* are dimensions for 42” deep 4 post racks
Adjustable EIA Mounting Rails
All 4 rails are fully adjustable. To set depth loosen (3)5/16”-18 X
3/4” Mounting bolts and slide to desired position.
Retighten to 20
foot pounds to engage washers.
Bolt Orientation
Panduit recommends putting the front rails 1” back for optimal ther-
mal and cable management.
Front rails are to be recessed less than 1.5” to be compatible with
newer thermal ducts.