Panduit PN380 Скачать руководство пользователя страница 8

PANDUIT

 DPoE Power System User’s Guide 

 

Issue 1.0 

 

 

Part Number: PN380 

 

 

Package Contents 

The DPoE Power system chasses (

PANDUIT

 part number DPoEPWRCM or DPoEPWRCU) are shipped 

with the following included items. 
 

Table 2: Package Contents 

Item 

Quantity 

Notes 

DPoE Power System User’s Guide 

This document.  PANDUIT part number PN380  

Cord Brackets 

For securing the individual power cords to the rear 
of the DPoE Power System Chassis 

Screws with integrated washers 

For securing the DPoE Power System chassis to 
a 19” rack 

Nuts 

For securing the lugs to the bulk DC connection 
on the rear of the DPoE Power System chassis 

Screws with integrated washers 

#4-40 screws for securing the cord brackets to the 
back of the DPoE Power system chassis 

CD-ROM 

Element Management Software for the DPoE 
Power System (included with DPoEPWRCM only) 

 

NOTE: 

GMT fuses, which are installed as part of installing the DPoE Power 
System, are NOT included with the shipment.  Fuses can be ordered in 
packages of 10 from 

PANDUIT

 (part number DPoEPWRF10).  Fuses are 

also available from Littelfuse

®

 and Bussman

®

.  Their part numbers are as 

follows: 
Littelfuse

®

 481 series 10 Amp fuse; part number 0481010 

Bussman

®

 Fast-Acting Indicating fuse; part number GMT-10A

 

 

 

Heat Dissipation 

The following table displays the maximum and typical British Thermal Units per hour (BTU/hr) of heat 
dissipated from each rectifier.  The maximum is calculated at 90 VAC, and typical is calculated at 230 
VAC. 
 

Table 3: Heat Dissipation 

Part Number 

Typical BTU/hr 

Max BTU/hr 

DPoEPWRR500 249 

410 

DPoEPWRR1250 451 

833 

 

AC Input Wiring 

The DPoE Power System chassis uses an individual AC feed architecture (See 

Figure 1: Individual AC 

Feed Wiring Architecture

), which requires one AC feed per rectifier. The, up to three, AC connections are 

made using the IEC320 receptacles on the rear of the chassis (See 

Figure 6: Chassis (Rear View) - AC 

Connections

).   

 
Connect each feed, using the appropriate power cord as listed in 

Table 1: DPoE Power Components 

Available 

 into the appropriate receptacle on the back of the system.  Cord securing brackets are included 

to secure the AC plugs to the chassis (See 

Figure 7: Securing Cord Bracket to Chassis

).   

 

 

 

 

 

3

 

 

Содержание PN380

Страница 1: ...DPoE Power System User s Guide Issue 1 0 Part Number PN380 February 2005 2005 PANDUIT Corp All Rights reserved www panduit com...

Страница 2: ...lies with Part 15 of FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 This device must accept any interference received including i...

Страница 3: ...implied PANDUIT Corp specifically disclaims the implied warranties of merchantability and fitness for a particular purpose The remedies provided herein are Buyer s sole and exclusive remedies PANDUIT...

Страница 4: ...rt Circuit and Current Limit 12 Troubleshooting 12 NIC Information 12 NIC Card Settings 13 Figures Figure 1 Individual AC Feed Wiring Architecture 4 Figure 2 DC Wire Diagram 5 Figure 3 Connecting to a...

Страница 5: ...on 3 Table 4 Recommended AC Circuit Breaker and Wire Sizes 4 Table 5 Minimum Recommended DC AWG for 90 C Cabling for Unprotected Outputs 7 Table 6 Recommended Torque Settings 7 Table 7 PANDUIT Corpora...

Страница 6: ...pport all the Powered Devices PD connected to the panel In these cases or in cases of multiple DPoE Power Patch Panels a larger power system is often required One option is to use the PANDUIT DPoE Pow...

Страница 7: ...ch chassis should be fed from a dedicated AC branch circuit of a TN or IT power system CAUTION The plug ends on the power cords used for the AC connections are considered to be the primary disconnect...

Страница 8: ...s of 10 from PANDUIT part number DPoEPWRF10 Fuses are also available from Littelfuse and Bussman Their part numbers are as follows Littelfuse 481 series 10 Amp fuse part number 0481010 Bussman Fast Ac...

Страница 9: ...5 14 DC Output Wiring Sizing There are two main considerations for sizing DC wire ampacity and voltage drop Ampacity refers to the safe current carrying level as specified by U S based organizations s...

Страница 10: ...rews The bulk DC connection may be used as a battery input or as an unfused bulk output The connections require a terminal lug 1 4 single hole lug with a max tongue width of 0 63 or less Size wires ba...

Страница 11: ...e included power harness has two wires for the A feed power only pins 1 2 The DPoE Power Patch Panel supports an optional redundant B feed power option but the terminals and wire leads are not attache...

Страница 12: ...with a minimum number of commonly available tools 1 2 flat blade and Phillips head screwdrivers Torque wrench 7 16 socket drive Wire and cable strippers PANDUIT part number CT 100 Wire and cable crimp...

Страница 13: ...ng boxes until the chassis wiring is complete Power Plant Mounting and Wiring WARNING Ensure all AC and DC power sources are off and disconnected Mechanical Mounting The DPoE Power System chassis is i...

Страница 14: ...wer System User s Guide Issue 1 0 Part Number PN380 IEC320 AC cord Cord Bracket Securing Screw Figure 5 Cord Bracket Figure 6 Chassis Rear View AC Connections 4 40 Screws Figure 7 Securing Cord Bracke...

Страница 15: ...C connection requires properly crimped terminal lugs 1 4 single hole lug with a max tongue width of 0 63 or less Terminal lugs such as PANDUIT part number LCA4 14 L for use with 3 or 4 AWG stranded wi...

Страница 16: ...lease the latch handle Pull the latch handle until the rectifier clears the rear connector on the chassis then gently slide it out of the rear connector With the latch handle open on the replacement r...

Страница 17: ...latched into their respective slots Make sure all power and signal connectors are properly mated Table 8 Troubleshooting Alarm Problem Possible Solution DC OK LED is extinguished This rectifier has s...

Страница 18: ...Power System EMS Webpage via IPSetup exe on the CD provided with the chassis DPoEPWRCM only The NIC card will also work with Telnet or SNMP NIC Card Settings The NIC card comes equipped with the follo...

Страница 19: ...ature sensing device to use for battery temperature compensation Internal sensor or external temperature probes The controller will autosense when an external probe is attached and automatically adjus...

Страница 20: ...t Number PN380 15 Parameter Description Default Setting High temperature alarm release NIC Card only The temperature value at which the controller will release a HIGH TEMP alarm For systems using the...