INSTRUCTIONS CM429A

For Instructions in Local Languages

and Technical Support:

www.panduit.com/resources/install_maintain.asp

E-mail:

[email protected]

Fax

:

(708)444-6448

www.panduit.com

Page 4 of 4

Routing of Switch Power Cable

NOTE:

  Dashed outline of 1 RU Switch is shown for power cord routing reference only.

            DO NOT INSTALL SWITCH AT THIS TIME.  

Cabinet and equipment rails are not shown to add clarity to view.

Prior to switch installation, route power cord through Switch Ducting and Switch Support Bracket as shown.  Slit grommet(s) along guide 
lines as needed to allow for power cord pass-through.  Use bridge features on Switch Support Bracket as tie-down point(s) to secure 
switch power cord to Switch Support Bracket with cable tie.

Switch Ducting

Switch 
Support 
Bracket

Install Switch

NOTE:

  Cabinet and equipment rails are not shown to add clarity to view.

Slide the 1 RU Switch onto positioning flanges of Switch Support Bracket.  Carefully insert inlet side of switch into rear opening of Switch 
Ducting.  Position holes of 1 RU Switch rack mount brackets over threaded studs of Switch Support Bracket.  Secure switch to Switch Sup-
port Bracket with (4) #10-32 acorn nuts 

(use 3/8” socket wrench).

Switch Power Cord

(to rear-mounted power 
outlet unit)

FRONT OF CABINET

REAR OF CABINET

Slit Grommet(s) along guide lines as needed 
to allow  for power cord pass-through

Bridge Feature

(use as tie-down 
point for cable tie)

FRONT OF CABINET

1 RU Switch

(reference; port side of 
switch faces Hot Aisle)

Positioning 

Flange

Rear Opening of 

Switch Ducting

(4) #10-32 Acorn Nuts

(use 3/8” socket wrench)

Positioning 

Flange

Switch Power Cord

REAR OF 
CABINET

Содержание CDE2

Страница 1: ...cting with hinged Perforated Door Page 1 of 4 Component Guide TOOL LIST 2 Philliips Screwdriver 5 16 Socket Wrench 3 8 Socket Wrench 1 4 Socket Driver 1 Hardware Kit not shown 1 Switch Support Bracket CDE2 installed in Net Access Server Cabinet Modular ToR Switch Inlet Duct CDE2 Cisco Nexus 2000 Series Switch reference ...

Страница 2: ... installed prior to switch installation and are designed to support the switch CDE2 ducting system ONLY requires use of primary Cisco rack mount brackets Cisco supplied switch cradle or extension brackets are not compatible with CDE2 Grounding Cage Nut green Cage Nut installed Intended Mounting Location 2 rack spaces 1 RU Switch reference port side of switch faces Hot Aisle Install Cage Nuts Inser...

Страница 3: ... use 5 16 socket wrench Switch Ducting Perforated Door of Switch Ducting faces Cold Aisle Install Switch Support Bracket Position Switch Support Bracket so that the mounting holes of Switch Support Bracket align with cage nuts in equipment rails installed on page 2 Secure Switch Support Bracket to equipment rails using 1 12 24 Phillips screw and 1 hex head grounding screw green use 5 16 socket wre...

Страница 4: ...ket with cable tie Switch Ducting Switch Support Bracket Install Switch NOTE Cabinet and equipment rails are not shown to add clarity to view Slide the 1 RU Switch onto positioning flanges of Switch Support Bracket Carefully insert inlet side of switch into rear opening of Switch Ducting Position holes of 1 RU Switch rack mount brackets over threaded studs of Switch Support Bracket Secure switch t...

Отзывы: