INSTRUCTIONS CM429A

For Technical Support: www.panduit.com/resources/install_maintain.asp

Page 3 of 4

Install Switch Ducting

Position Switch Ducting so that the perforated door of ducting faces the cold aisle and the mounting holes of Switch Ducting align with 
cage nuts in equipment rails 

(installed on page 2)

.  Secure Switch Ducting to equipment rails using (1) #12-24 Phillips screw and (1) hex 

head grounding screw 

(green; use 5/16” socket wrench)

 per rail.  Ensure that hex head grounding screws fasten into grounding cage nuts.

(2) #12-24 Hex Head 
Grounding Screws

(use 5/16” socket wrench)

Switch Ducting

Perforated Door of Switch Ducting

(faces Cold Aisle)

Install Switch Support Bracket

Position Switch Support Bracket so that the mounting holes of Switch Support Bracket align with cage nuts in equipment rails 

(installed on 

page 2)

.  Secure Switch Support Bracket to equipment rails using (1) #12-24 Phillips screw and (1) hex head grounding screw 

(green; use 

5/16” socket wrench)

 per rail.  Ensure that hex head grounding screws fasten into grounding cage nuts.

Grounding Cage Nuts

(green)

Cage Nuts

(installed)

(2) #12-24 Phillips Screws

(2) #12-24 Hex Head 
Grounding Screws

(use 5/16” socket wrench)

(2) #12-24 Phillips Screws

Cage Nuts

(installed)

Grounding Cage Nuts

(green)

Switch Support 
Bracket

FRONT OF 
CABINET

REAR OF 
CABINET

FRONT OF 
CABINET

Содержание CDE2

Страница 1: ...cting with hinged Perforated Door Page 1 of 4 Component Guide TOOL LIST 2 Philliips Screwdriver 5 16 Socket Wrench 3 8 Socket Wrench 1 4 Socket Driver 1 Hardware Kit not shown 1 Switch Support Bracket CDE2 installed in Net Access Server Cabinet Modular ToR Switch Inlet Duct CDE2 Cisco Nexus 2000 Series Switch reference ...

Страница 2: ... installed prior to switch installation and are designed to support the switch CDE2 ducting system ONLY requires use of primary Cisco rack mount brackets Cisco supplied switch cradle or extension brackets are not compatible with CDE2 Grounding Cage Nut green Cage Nut installed Intended Mounting Location 2 rack spaces 1 RU Switch reference port side of switch faces Hot Aisle Install Cage Nuts Inser...

Страница 3: ... use 5 16 socket wrench Switch Ducting Perforated Door of Switch Ducting faces Cold Aisle Install Switch Support Bracket Position Switch Support Bracket so that the mounting holes of Switch Support Bracket align with cage nuts in equipment rails installed on page 2 Secure Switch Support Bracket to equipment rails using 1 12 24 Phillips screw and 1 hex head grounding screw green use 5 16 socket wre...

Страница 4: ...ket with cable tie Switch Ducting Switch Support Bracket Install Switch NOTE Cabinet and equipment rails are not shown to add clarity to view Slide the 1 RU Switch onto positioning flanges of Switch Support Bracket Carefully insert inlet side of switch into rear opening of Switch Ducting Position holes of 1 RU Switch rack mount brackets over threaded studs of Switch Support Bracket Secure switch t...

Отзывы: