AT-OME-RX21
22
webGUI
Select System from the top navigation to adjust relay, network, or system options.
System
Relay
Control
- Set the relay to either follow the display’s status (on: c1-close c2-open, off: c1-open c2-close) or be
manually set using the selectors in the webGUI.
Relay -
When the relay is set to manual, select the sliders to open and close the com ports.
Type
- Switch between pulse and closed relay type.
Pulse Time -
Sets the time between each pulse in seconds. Range is 1 to 30. Default is 1.
When using a dual signal relay with an electric projection screen, it
allows for two different circuits to be controlled: up and down
(pictured to the right)
.
The relay will default to follow the display. When the unit turns on the
relay will close C1 and open C2. When the display is turned off and
signal is no longer being received C1 will open and C2 will close.
C1
C1
C2
C2
COM
COM
Down
Closed
Open
Open
Closed
Up
NOTE:
When the unit is set to pulse, the relay will latch for the designated pulse time before opening
again. The relay that opens and closes will be determined by the power state.
Power on
Relay 1: Latch will close for designated pulse time then open.
Relay 2: Relay will remain open.
Power Off
Relay 1: Relay will remain open.
Relay 2: Latch will close for designated pulse time then open.