117
Control detail:
During operation ON at Heat Mode
-
Boiler signal turns ON when
a. Outdoor ambient < Outdoor Ambient Set
AND
b. Buffer tank temperature < Target Buffer Tank Tempe [START_TEMP] for [START_TIMER]
AND
c. Heat pump operate at room side
AND
d. Connection of Boiler to Heating Select "YES" From installer menu
AND
e. Buffer Tank connection select "YES"
AND
f. Boiler prohibit flag = 0
-
Boiler signal turns OFF when
a. Outdoor ambient > Outdoor Ambient Set + [-2°C]
OR
b. Buffer Tank temperature > Target Buffer Tank tempe [STOP_TEMP] for [STOP_TIMER]
OR
c. Heat pump not at room side.
OR
d. Boiler prohibit flag = 1
During operation ON at Tank Mode
-
Boiler signal turns ON when
a. Outdoor ambient < Outdoor Ambient Set
AND
b. Heat pump operate at tank side for continuous | DELAY_TIMER |
AND
c. Connection of Boiler to DWH Tank select "YES" from installer menu.
AND
d. Boiler prohibit flag = 0
-
Boiler signal turns OFF when
a. Outdoor ambient > Outdoor Ambient Set + [2°C]
OR
b. Heat pump not operates at tank side.
OR
c. Boiler prohibit flag = 1
Boiler prohibit flag control
Purpose:
-
For product safety. Boiler signal is OFF when water temperature is too high.
Start condition:
a. Water outlet ≥ 85°C continues for 5 minutes.
b. Water inlet ≥ 85°C continues for 5 minutes.
c. Zone1 water temp ≥ 85°C continues for 5 minutes.
d. Zone2 water temp ≥ 85°C continues for 5 minutes.
Contents:
After start condition fulfilled, set boiler prohibit flag = 1
Cancel condition:
-
After 30 minutes from start condition fulfilled.
Contents:
Set boiler prohibit flag = 0