16.5.6 Outdoor High Pressure Abnormality (H64)
Malfunction Decision Conditions:
During operation of cooling and heating, when the outdoor high pressure sensor output signal is 0 Vdc or 5 Vdc.
Malfunction Caused:
1 Faulty
connector
connection.
2 Faulty
sensor.
3 Faulty outdoor unit PCB (main).
Abnormality Judgment:
Continue 4 times in 20 minutes.