115
16.5.23
Four Way Valve Abnormality (F25)
Malfunction Decision Conditions:
1 During heating operation, when the indoor pipe temperature of thermostat ON indoor unit < 0°C.
2 During cooling operation, when the indoor pipe temperature of thermostat ON indoor unit > 45°C.
Malfunction Caused:
1 Faulty
sensor.
2 Faulty
connector
connection.
3 Faulty outdoor unit PCB (noise filter/main).
4 Faulty four way valve.
Abnormality Judgment:
Continue 4 times in 30 minutes.
Содержание WH-SXC16F9E8
Страница 28: ...28 10 1 2 Solar Printed Circuit Board Optional ...
Страница 46: ...46 57 C 57 C 57 C 57 C ...
Страница 47: ...47 ...
Страница 53: ...53 ...
Страница 54: ...54 ...
Страница 55: ...55 57 C 57 C 50 C 50 C ...