Control contents:
1) After fulfil start condition, indoor will operate the force heater operation according to below mode condition
Heat mode Only
: Turn ON backup heater to achieve room heat pump target water temperature.
Heat + Tank mode
: Turn ON backup heater to heat up room
OR
Turn ON Heater to Boil up tank water.
Cool mode Only
: Water pump and backup heater will OFF in force heater mode
Cool + Tank mode
: Operate pump and internal Heater OR External heater to Boil up tank water.
Tank mode Only
: Operate pump and internal Heater OR External heater to Boil up tank water.
* For heat mode condition, backup heater will only turn ON if the backup heater is enable regardless of Room
Heater Selection
* For tank mode condition, If internal heater selected backup heater will turn ON to boil up tank water.
If external heater selected, booster heater will turn ON to boil up tank water regardless of tank heater
selection
Room Side: (Heat Mode)
1) When force heater mode start condition fulfilled, turn ON water pump and turn ON backup heater follow
below control.
2) Operate the 3 ways valve at room side only and turn ON 2 ways valve as heat mode operation.
3) Turn ON the zone pump and mixing valve if system select 2 zone system or Buffer tank connect YES, control
according to normal zone pump and mixing valve control.
4) When Force heater mode stop condition fulfilled, turn OFF heater as below condition and turn OFF water
pump after pump delay time.
Backup Heater On Condition:
a) When Force Heater Control start condition fulfill
AND
b) After water pump operate 2 minute
AND
c) When water outlet temperature < water set tempe [Remote Control Heater ON Setting]
AND
d) 20 minutes since previous Backup heater Off
AND
e) Backup Heater Enable
Backup Heater Stop condition
a) Force mode off
OR
b) Operation off
OR
c) When water outlet temperature > water set tempe [Remote Control Heater OFF Setting] for
continuous 15 secs
OR
* ON/OFF follow normal heater sequence.
Tank side (Tank mode)
1) When tank mode select and force heater bit received, turn ON backup heater (INTERNAL) or Booster Heater
(External) depend on the tank heater selection.
2) If tank heater selection is INTERNAL, follow normal thermo judgement to switch 3 ways valve to tank side
and room side.
3) If tank heater selection is EXTERNAL, only turn ON booster heater according to tank thermo.
Tank Heater selection is INTERNAL:
Backup Heater ON Condition:
a) After water pump operate 2 mins
AND
b) When tank temperature < Tank set temperature - [Remocon Set Tank Re-heat Temp]
AND
c) 20 minutes since previous backup heater OFF
AND
d) Backup heater enable
Backup Heater OFF Condition:
a) Force mode OFF
OR
b) When tank temperature > Tank set temperature for continuous 15 secs
OR
c) Tank Operation OFF