Connect the Cable to Mono Bloc Unit
WARNING
This section is for authorised and licensed electrician only. Work behind the cabinet front plate secured by screws must only be carried out
under supervision of qualified contractor, installation engineer or service person.
Remove The Cabinet Front
Plate
1. Remove the 5 mounting screws as shown in the
illustration.
2. Slide the cabinet front plate downward to release
the pawls.
Then, pull it toward front to remove it.
Remove The Cabinet Top Plate
1. Remove the 12 mounting screws as shown in the
illustration.
2. Lift the cabinet top plate upward to remove it.
Fixing of Power Supply Cord
(REFER TO WIRING DIAGRAM AT UNIT FOR DETAIL)
1. An isolating device must be connected to the power supply cable.
o
Isolating device (Disconnecting means) should have minimum 3.0 mm contact gap.
o
Connect the approved polychloroprene sheathed power supply 1 cord and power supply 2 cord and type
designation 60245 IEC 57 or heavier cord to the terminal board, and to the other end of the cord to isolating
device (Disconnecting means). See below table for cable size requirement.
Model
Power Supply Cord
Cable Size Isolating
Devices
Recommended
RCD
WH-MDC05H3E5
1
3 x min 1.5 mm
2
15/16A
30mA, 2P, type A
2
3 x min 1.5 mm
2
15/16A
30mA, 2P, type AC
WH-MDC07H3E5 and WH-MDC09H3E5
1
3 x min 2.5 mm
2
25A
30mA, 2P, type A
2
3 x min 1.5 mm
2
15/16A
30mA, 2P, type AC
2. To avoid the cable and cord being damaged by sharp edges, the cable and cord must be passed through the
designated holes before being connected to the terminal block.
3. Secure the cable onto the control board with the holder (clamper).
Wire Stripping and Connecting Requirement
Mounting screws
Mounting
screws
Cabinet front plate
f
Cabinet top plate
6
Mounting
screws
Terminal on the Mono bloc unit
L
N
L
1
N
1
(Power Supply Cord)
Terminals on the isolating device from
power supply (Disconnecting means)
L
N
L
1
N
1
Power Supply 2
Power Supply 1
Terminal screw
Tightening torque
cN•m {kgf•cm}
M4
157~196 {16~20}
M5
196~245 {20~25}
*1 - Earth wire must be longer than other cables
for safety reasons.
Power Supply Cord
*1
5 mm or
more
(gap between wires)
Terminal
board
Wire stripping
No loose strand
when insert
10 ±
1
m
m
ACCEPT
Conductor
over insert
Conductor not
fully insert
Conductor
fully insert
PROHIBITED
PROHIBITED