Installation manual
18
U-5~48MX3
Urban Multi air conditioner
4PW16235-1C
Procedure for checking maximum concentration
Check the maximum concentration level in accordance with steps 1
to 4 below and take whatever action is necessary to comply.
1
Calculate the amount of refrigerant (kg) charged to each system
separately.
2
Calculate the smallest room volume (m
3
)
In a case such as the following, calculate the volume of (A), (B)
as a single room or as the smallest room.
3
Calculating the refrigerant density using the results of the
calculations in steps 1 and 2 above.
If the result of the above calculation exceeds the maximum
concentration level then make similar calculations for the second
then third smallest room and so until the result falls short of the
maximum concentration.
4
Dealing with the situations where the result exceeds the
maximum concentration level.
Where the installation of a facility results in a concentration in
excess of the maximum concentration level then it will be
necessary to revise the system.
Please consult your supplier.
N
OTES
amount of
refrigerant in a
single unit system
(amount of
refrigerant with
which the system is
charged before
leaving the factory)
+
additional charging
amount (amount of
refrigerant added
locally in
accordance with the
length or diameter of
the refrigerant
piping)
=
total amount of
refrigerant (kg) in
the system
NOTE
Where a single refrigerant facility is divided into
2 entirely independent refrigerant systems, use the
amount of refrigerant with which each separate system
is charged.
A.
Where there are no smaller room divisions
B.
Where there is a room division but there is an
opening between the rooms sufficiently large to
permit a free flow of air back and forth.
1
opening between rooms
2
partition
(Where there is an opening without a door or where there are
openings above and below the door which are each equivalent in
size to 0.15% or more of the floor area.)
total volume of
refrigerant in the
refrigerant system
size (m
3
) of smallest
room in which there is
an indoor unit installed
≤
maximum concentration level (kg/m
3
)
1
2