Installation manual

16

U-5~48MX3

Urban Multi air conditioner

4PW16235-1C

8. B

EFORE

 

OPERATION

8.1.

Checks before initial start-up

After the installation, check the following before switching on the
circuit breaker:

1

The position of the switches that require an initial setting

Make sure that switches are set  according to your application
needs before turning the power supply on.

2

Power supply wiring and transmission wiring

Use a designated power supply and transmission wiring and
make sure that it has been carried out according to the
instructions described in this manual, according to the wiring
diagrams and according to local and national regulations.

3

Pipe sizes and pipe insulation

Make sure that correct pipe sizes are installed and that the
insulation work is properly executed.

4

Additional refrigerant charge

The amount of refrigerant to be added to the unit should be
written on the included “Added Refrigerant” plate and attached
to the rear side of the front cover.

5

Insulation test of the main power circuit

Using a megatester for 500 

V, check that the insulation

resistance of 2 M

 or more is attained by applying a voltage of

500 V DC between power terminals and earth. Never use the
megatester for the transmission wiring.

6

Installation date

Be sure to keep record of the installation date on the sticker on
the rear of the upper front panel according to EN60335-2-40.

8.2.

Test run

Power supply connection

When running the unit for the first time after installation, be sure to
perform a test run following these steps for test run. (Not performing
a test run when the unit is first installed may prevent the unit from
operating properly.)

During the operation, monitor the outdoor unit operation status
and check for any incorrect wiring. 

(See figure 19)

<Cautions for check operation>

If the system is started within about 12 minutes after the
outdoor/indoor units are turned ON, the compressor will not run
and H2P lights up. Before starting an operation, always verify
that the LED display shows the contents of the table in 

"8.2. Test

run" on page 16

.

The system may require up to 10 minutes until it can start the
compressor after an operation start. This is a normal operation
to equalize the refrigerant distribution.

The check operation does not provide any means of checking
the indoor units individually. For that purpose, perform normal
operation using the remote controller after the check operation.

Make sure that the circuit breaker on the power supply
panel of the installation is switched off.

Attach the power wire securely.

Introducing power with a missing N-phase or with a
mistaken N-phase will break the equipment.

After completing installation, be sure to open the valve.
(Operating the unit with the valve shut will break the
compressor.)

Turn ON the power to the outdoor units 
and indoor units.

Make sure to turn ON the power 6 
hours before starting the operation. 
This is necessary to warm the 
crankcase preliminarily by the electric 
heater.

Check the LED on the P-board (A1P) in the outdoor unit to see if the data 
transmission is performed normally.

• As necessary, configure the system 

settings on-site by using the dipswitch 
(DS1) on the outdoor unit P-board 
(A1P) and push button switches 
(BS1~5).

• When the system is in the multiple-

outdoor unit configuration (Out 
Multi), perform the configuration on 
the parent unit. (Any settings made 
on a child unit will be ignored.)

Always perform configuration after 
turning ON the power. To learn the 
setting method, refer to the [Service 
precautions] label attached at the 
position shown in 

figure 19

 (Electric box 

lid in outdoor unit). (Remember, the 
actual settings you have made must be 
recorded on the [Service Precautions] 
label.)

Check if the stop valves are in 
appropriate status and correct any 
wrong status. (Refer to the table in 

"6.6. Additional refrigerant charge" on 
page 10

.)

CAUTION
Do not leave any stop valve closed. 
Otherwise the compressor will fail.

Perform the check operation following 
the instructions printed on the [Service 
Precaution] label.

The system operates for about 15 
minutes (30 minutes at maximum) and 
automatically stops the test operation. 
The system can start a normal 
operation about 15 minutes after the 
test operation, only if the remote 
controller displays no error codes.

1

Electric box lid

2

Location of the service precautions label

3

Location of the caution label

Led display (Default 

status before delivery)

Micro-

computer 
operation 

monitor

Page

Ready/

Error

Cooler/heater changeover

Low 

noise

Demand

Multi

Individual

Bulk 

(parent)

Bulk 

(child)

HAP

H1P

H2P

H3P

H4P

H5P

H6P

H7P

H8P

One outdoor unit 

installed

When 

multiple 
outdoor 

unit 

installed

(*)

Master 
station

Sub 

station 1

Sub 

station 2

LED display: 

 OFF 

 ON 

 Blinking

(*)

The base (parent) unit is the outdoor unit to which the interconnecting wiring for 
the indoor units is connected. The other outdoor units are child units.

Содержание U-5MX3XPQ

Страница 1: ...14MX3XPQ A U 16MX3XPQ A U 18MX3XPQ U 20MX3XPQ U 22MX3XPQ U 24MX3XPQ U 26MX3XPQ U 28MX3XPQ U 30MX3XPQ U 32MX3XPQ U 34MX3XPQ U 36MX3XPQ U 38MX3XPQ U 40MX3XPQ U 42MX3XPQ U 44MX3XPQ U 46MX3XPQ U 48MX3XPQ...

Страница 2: ...D c H h h1 h2 1500 1 3 5 4 2 2 mm 6 3 1 0 0 0 1 0 0 0 1000 1 50 0 1500 1500 722 737 80 80 765 A B 1 2 4 5 6 7 3 7 1 6 1 2 4 5 3 5 3 3 2 1 5 3 3 1 3 3 4 4 4 4 9 4 4 5 7 7 5 5 2 5 5 5 5 6 2 6 9 2 2 6 6...

Страница 3: ...4 5 6 7 17 8 12 20 18 18 1 2 1 2 5 3 3 3 3 5 5 5 7 5 4 4 4 4 4 6 A B F2 F2 F1 F1 A B C Q1Q2 1 4 3 2 2 6 6 6 5 1 2 3 3 4 4 5 6 3 4 3 4 6 3 4 6 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 2 1 A B C A B C F1 F2 F1 F2...

Страница 4: ...16 17 18 5 1 7 10 3 2 9 6 6 6 6 7 4 11 8 6 6 6 6 6 6 7 7 9 8 4 11 6 6 1 10 3 2 6 6 6 6 18 TO IN D UNIT F1 F2 DS1 1 2 3 4 OFF ON O U T I N F1 F2 F1 F2 F1 F2 1 A B C A B C 1 DS1 1 2 3 4 OFF ON O U T I N...

Страница 5: ...0A refer to the product catalogs Total capacity quantity of indoor units U 5 48MX3 Urban Multi air conditioner Installation manual READ THIS MANUAL ATTENTIVELY BEFORE STARTING UP THE UNIT DO NOT THROW...

Страница 6: ...fer to figure 1 and choose one of the possibilities In case of an installation site where only the sides A B have obstacles the wall heights have no influence on any indicated service space dimensions...

Страница 7: ...uipment personal computers etc See figure 2 In extreme circumstances you should keep distances of 3 m or more and use conduit tubes for power and transmission lines In heavy snowfall areas select an i...

Страница 8: ...frigerant All field piping must be installed by a licensed refrigeration technician and must comply with relevant local and national regulations CAUTION TO BE TAKEN WHEN BRAZING REFRIGERANT PIPING Do...

Страница 9: ...recommended pipe size is not available stick to the original pipe diameter which may result in a small capacity decrease Cautions for installation of multiple outdoor units 1 The piping between the o...

Страница 10: ...e outdoor unit connecting pipe kits or between the outdoor units exceeds 2 m create a rise of 200 mm or more in the gas line within a length of 2 m from the kit If 2 m If 2 m A Unit A B Unit B C Unit...

Страница 11: ...t 8 i 40 m Refrigerant branch kit selection Refrigerant branch kits can only be used with R 410A How to select the line branch pipe When using line branch pipe at the first branch counted from the out...

Страница 12: ...unit is U 34MX3 and the piping lengths are as below R 30x0 25 10x0 17 10x0 11 40x0 054 49x0 022 6 7 538 R 7 5 kg A B C D Outdoor unit capacity type Piping size outer diameter Gas pipe Liquid pipe U 5...

Страница 13: ...backseat type Always use the special tool 3 Make sure to tighten the cap securely Closing stop valve 1 Remove the cap and turn the valve clockwise with the hexagon wrench 2 Securely tighten the valve...

Страница 14: ...e additional refrigerant to be charged on page 8 and fill in the amount in the Additional refrigerant charge label attached to the unit After the vacuum drying is finished charge the additional refrig...

Страница 15: ...oor unit installed See figure 9 1 Fully open the gas line stop valve oil equalizing line stop valve liquid line stop valve and valves A and B above must be left fully closed start the additional refri...

Страница 16: ...ection wiring to outdoor outdoor transmission F1 F2 outdoor indoor transmission F1 F2 outdoor multi transmission Q1 Q2 refer to 7 5 Examples on page 13 For connection wiring to the central remote cont...

Страница 17: ...n earth leak detector capable of handling high harmonics needs to be used in order to prevent malfunctioning of the earth leak detector itself Earth leak detector which are especially for protecting g...

Страница 18: ...torque for the terminal screws Precautions when connecting the ground When pulling the ground wire out wire it so that it comes through the cut out section of the cup washer An improper ground connect...

Страница 19: ...The interconnecting wiring between the outdoor units must be 30 m See the paragraph Fixing field line connection on page 14 A Electric wiring diagram Printed on the back of the electric box lid 1 Cut...

Страница 20: ...y For that purpose perform normal operation using the remote controller after the check operation Make sure that the circuit breaker on the power supply panel of the installation is switched off Attac...

Страница 21: ...entration level is required According to the appropriate European Standard the maximum allowed concentration level of refrigerant to a humanly space for R 410A is limited to 0 44 kg m3 Pay special att...

Страница 22: ...of the maximum concentration level then it will be necessary to revise the system Please consult your supplier NOTES amount of refrigerant in a single unit system amount of refrigerant with which the...

Страница 23: ...NOTES NOTES...

Страница 24: ...4PWEN16235 1C...

Отзывы: