Outdoor Unit Repair Procedures
3
2. Discharging Compressor Oil
2-2. Discharging Oil in Compressor
Recover the refrigerant in the outdoor unit following the procedures in “4. Recovering Refrigerant.” Remove the
compressor and discharge the oil in it. Refer to “9. Compressor” for detailed procedures.
2-3. Checking the Oil
Acceptance/rejection criteria for the oil
Condition of
refrigeration cycle
Condition of oil
Judgment criteria for changing oil*
Color
Odor
Total acid value
Hue
Normal
Yellowish
None
0.02 or less
3.5 or less
Abnormal overheat-
operation
Brownish
Smells somewhat
(not as strong as below)
over 0.06
over 4.0
Changing the oil and system cleaning
with dry-cores are necessary.
Motor burnout
Brownish /
blackish
Pungent / burnt odor
Changing the oil and system cleaning
with dry-cores are necessary.
* It is difficult to measure the total acid value in the field, therefore oil hue and odor are the rule of thumb.
Checking for carbon deposits and abrasive metal powder can additionally be used to assess the system condition.
Fig. 2-d
High-pressure outlet port
(for ø7.94mm-dia connector)
Low-pressure outlet port
(for ø7.94mm-dia connector)
Liquid tube service port
(for ø7.94mm-dia connector)
Gas tube service port
(for ø7.94mm-dia connector)
Type 18HP / 20HP
Nitrogen gas
Manifold gauge
Lo
Hi
Packless valve or the like
Container
Oil balance tube service port
(For 7.94mm-dia. connector)
SM830204-05_2WAY SYS_new.indb 5
15/01/05 15:31:28