4. ELECTRICAL
WIRING
4-1. General Precautions on Wiring
(1) Before wiring, confirm the rated voltage of the unit as
shown on its nameplate, then carry out the wiring closely
following the wiring diagram.
(2) Circuit breaker must be incorporated in the fixed wiring in
accordance with the wiring regulations. The circuit breaker
must be an approved 10-16 A, having a contact separation
in all poles.
(3) To prevent possible hazards from insulation failure, the unit
must be grounded.
(4) Each wiring connection must be done in accordance with
the wiring system diagram. Wrong wiring may cause the
unit to misoperate or become damaged.
(5) Do not allow wiring to touch the refrigerant tubing,
compressor, or any moving parts of the fan.
(6) Unauthorized changes in the internal wiring can be very
dangerous. The manufacturer will accept no responsibility
for any damage or misoperation that occurs as a result of
such unauthorized changes.
(7) Regulations on wire diameters differ from locality to
locality. For field wiring rules, please refer to your LOCAL
ELECTRICAL CODES before beginning.
You must ensure that installation complies with all relevant
rules and regulations.
(8) To prevent malfunction of the air conditioner caused by
electrical noise, care must be taken when wiring as follows:
●
The remote control wiring and the inter-unit control wiring
should be wired apart from the inter-unit power wiring.
●
Use shielded wires for inter-unit control wiring between units
and ground the shield on both sides.
(9) If the power supply cord of this appliance is damaged,
it must be replaced by a repair shop designated by the
manufacturer, because special-purpose tools are required.
4-2. Recommended Wire Length and Wire Diameter
for Power Supply System
Indoor unit
Type
(B) Power supply
Time delay fuse or
circuit capacity
2.5 mm
2
F1
Max. 130 m
10-16 A
Control wiring
(C) Inter-unit
(between outdoor
and indoor units)
control wiring
(D) Remote control
wiring
(E) Control wiring
for group control
0.75 mm
2
(AWG #18)
Use shielded wiring*
0.75 mm
2
(AWG #18)
0.75 mm
2
(AWG #18)
Max. 1,000 m
Max. 500 m
Max. 200 m (Total)
N OT E
* With ring-type wire terminal.
II̲09̲F616388̲EU̲L.indb 11
II̲09̲F616388̲EU̲L.indb 11
2013/12/11 15:12:25
2013/12/11 15:12:25
Содержание S-100PF1E5A
Страница 48: ...48 NOTE II 09 F616388 EU L indb 48 II 09 F616388 EU L indb 48 2013 12 11 15 12 40 2013 12 11 15 12 40 ...
Страница 72: ...72 NOTAS II 09 F616388 EU L indb 72 II 09 F616388 EU L indb 72 2013 12 11 15 12 51 2013 12 11 15 12 51 ...
Страница 96: ...96 ANMERKUNGEN II 09 F616388 EU L indb 96 II 09 F616388 EU L indb 96 2013 12 11 15 13 02 2013 12 11 15 13 02 ...
Страница 120: ...120 PROMEMORIA II 09 F616388 EU L indb 120 II 09 F616388 EU L indb 120 2013 12 11 15 13 12 2013 12 11 15 13 12 ...
Страница 144: ...144 MEMO II 09 F616388 EU L indb 144 II 09 F616388 EU L indb 144 2013 12 11 15 13 24 2013 12 11 15 13 24 ...
Страница 168: ...168 NOTAS II 09 F616388 EU L indb 168 II 09 F616388 EU L indb 168 2013 12 11 15 13 37 2013 12 11 15 13 37 ...
Страница 192: ...192 ΣΗΜΕIΩΜΑΤΆΡΙΟ II 09 F616388 EU L indb 192 II 09 F616388 EU L indb 192 2013 12 11 15 13 48 2013 12 11 15 13 48 ...