CAUTION
(1) When linking the outdoor units in a network, disconnect the terminal extended from the short plug from all outdoor units
except any one of the outdoor units.
(When shipping: In shorted condition.)
For a system without link (no wiring connection between outdoor units), do not remove the short plug.
(2) Do not install the inter-unit control wiring in a way that forms a loop. (Fig. 4-3)
Outdoor unit
Outdoor unit
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Prohibited
Prohibited
Indoor unit
Fig. 4-3
(3) Do not install inter-unit control wiring such as star branch wiring. Star branch wiring causes mis-address setting. (Fig. 4-4)
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
NO
Branch point
Fig. 4-4
(4) If branching the inter-unit control wiring, the number of branch points should be 16 or fewer.
Central Controller
Outdoor unit
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Outdoor unit
: Branch point
More than 2m required
Fig. 4-5
(5) Use shielded wires for inter-unit control wiring (c)
and ground the shield on both sides, otherwise
misoperation from noise may occur. (Fig. 4-6)
Connect wiring as shown in Section “4-3. Wiring System
Diagrams”.
Fig. 4-6
(6) • Connecting cable between indoor unit and outdoor
unit shall be approved polychloroprene sheathed 5 or
3 *1.5 mm
2
flexible cord. Type designation 60245 IEC 57
(H05RN-F, GP85PCP etc.) or heavier cord.
• Use the standard power supply cables for Europe (such
as H05RN-F or H07RN-F which conform to CENELEC
(HAR) rating specifications) or use the cables based on
IEC standard. (60245 IEC57, 60245 IEC66)
WARNING
Loose wiring may cause the terminal to overheat or result
in unit malfunction. A fire hazard may also occur. Therefore,
ensure that all wiring is tightly connected.
When connecting each power wire to the terminal, follow the
instructions on “How to connect wiring to the terminal” and
fasten the wire securely with the terminal screw.
Shielded wire
Ground
Ground
II̲09̲F616388̲EU̲L.indb 13
II̲09̲F616388̲EU̲L.indb 13
2013/12/11 15:12:25
2013/12/11 15:12:25
Содержание S-100PF1E5A
Страница 48: ...48 NOTE II 09 F616388 EU L indb 48 II 09 F616388 EU L indb 48 2013 12 11 15 12 40 2013 12 11 15 12 40 ...
Страница 72: ...72 NOTAS II 09 F616388 EU L indb 72 II 09 F616388 EU L indb 72 2013 12 11 15 12 51 2013 12 11 15 12 51 ...
Страница 96: ...96 ANMERKUNGEN II 09 F616388 EU L indb 96 II 09 F616388 EU L indb 96 2013 12 11 15 13 02 2013 12 11 15 13 02 ...
Страница 120: ...120 PROMEMORIA II 09 F616388 EU L indb 120 II 09 F616388 EU L indb 120 2013 12 11 15 13 12 2013 12 11 15 13 12 ...
Страница 144: ...144 MEMO II 09 F616388 EU L indb 144 II 09 F616388 EU L indb 144 2013 12 11 15 13 24 2013 12 11 15 13 24 ...
Страница 168: ...168 NOTAS II 09 F616388 EU L indb 168 II 09 F616388 EU L indb 168 2013 12 11 15 13 37 2013 12 11 15 13 37 ...
Страница 192: ...192 ΣΗΜΕIΩΜΑΤΆΡΙΟ II 09 F616388 EU L indb 192 II 09 F616388 EU L indb 192 2013 12 11 15 13 48 2013 12 11 15 13 48 ...