Failure Diagnosis
Failure Diagnosis of Inverter Unit
Before inspection or component replacement, always shut off the ground fault protector and take
suf
fi
cient time.
(Approx. 5 minutes are required for the capacitor to discharge)
(1) When the refrigeration unit stopped by activation of the ground fault protector,
possible cause is as follows. Check all of the following causes.
Cause
Method of Checking
Method of Action
Compressor failure
Check insulation resistance between each phase of
compressor and case.
Less than 1 M
Ω
indicates motor failure.
Replace the compressor
Check the winding resistance of the compressor.
0.97
Ω
to 1.01
Ω
(AT 25 °C) indicates no problem.
Replace the compressor
Failure of an electric
component other than
compressor
Check the insulation resistance between each
terminal of the INV-EN-PCB and ground (G
terminal). Less than 1 M
Ω
indicates insulation
failure of the INV-EN-PCB.
Replace the INV-EN-PCB
Be sure to eliminate the cause of the failure before supplying the power (turning the ground fault
protector ON).
Caution
Electrical box internal layout
(Top side)
Control
terminal
base
Power source
terminal base
Terminal Base for showcase
operation signal
Terminal Base for liquid tube
electromagnetic valve
Reactor
Caution