EN - 44
Failure Diagnosis
Error Code
Error code
Meaning
Cause
Method of Action (Listed)
E31
High pressure
abnormal
(1st to 6th time)
High pressure increased to abnormal level.
(1) Check the cause of high pressure abnormality.
(2) Check if abnormality exists in the high pressure
sensor.
E32
Refrigerant
fl
ood back
alarm
Suction gas superheat (difference between the
“suction gas temperature” and “evaporating
temperature converted from low pressure”)
became 1 K or below continuously for 2
minutes.
Check the cause of refrigerant
fl
ood back operation.
E57
Unit outlet temp sensor
abnormal
Unit outlet temp sensor became abnormal
(open condition).
(1) Check the connection of “2P4 U outlet connector” of
the control PCB.
(2) Check the resistance value of the unit outlet
temperature sensor.
E59
Gas cooler outlet temp
sensor abnormal
Gas cooler outlet temp sensor became
abnormal (open)
(1) Check the connection of “2P3 GC outlet connector” of
the control PCB.
(2) Check the resistance value of the gas cooler outlet
temperature sensor.
E60
Inverter abnormal (1st
to 9th time)
Input Current Sensor Fault
EEPROM Data Fault
See “E70”
E62
Inverter Over Current
(1st to 9th time)
Over Current (Inverter Output Current)
See “E72”
E64
Inverter
Over Load
(1st to 9th time)
Over Current (Inverter Input Current)
See “E74”
E66
Inverter
Step Out
(1st to 9th time)
Step Out
See “E76”
E68
PFC abnormal
(1st to 9th time)
PFC circuit Fault
See “E78”
E70
Inverter abnormal
(10th time)
Input Current Sensor Fault
EEPROM Data Fault
(1) Check the connection to the inverter PCB.
(2) Check whether abnormality occurred in the power
supply.
(3) Replace the inverter PCB
E72
Inverter
Over Current
(10th time)
Over Current (Inverter Output Current)
(1) Check the cause of overload operation.
(2) Check the connection line between the inverter PCB
and the compressor.
(3) Check whether abnormality occurred in the power
supply.
(4) Replace the inverter PCB.
E74
Inverter
Over Load
(10th time)
Over Current (Inverter Input Current)
(1) Check the cause of overload operation.
(2) Check the connection line between the inverter PCB
and the compressor.
(3) Check the connection the Power supply.
(4) Check whether abnormality occurred in the power
supply.
(5) Replace the inverter PCB.
E76
Inverter
Step Out
(10th time)
Inverter Step Out
(1) Check short cycle operation (frequent start/stop
operation).
(2) Check the connection line between the inverter PCB
and the compressor.
(3) Check the connection the Power supply.
(4) Check whether abnormality occurred in the power
supply.
(5) Replace the inverter PCB.
E78
PFC abnormal
(10th time)
PFC circuit Fault
(1) Check the connection the Power supply.
(2) Check whether abnormality occurred in the power
supply.
(3) Replace the inverter PCB.
E80
Split cycle outlet temp
sensor abnormal
Split cycle outlet temp sensor became
abnormal (open)
(1) Check the connection of "2P2 S outlet connector" of
the control PCB.
(2) Check the resistance value of the split outlet
temperature sensor.
E81
Intermediate pressure
sensor abnormal
Intermediate pressure sensor became
abnormal (open).
(1) Check the connection of "3P2 intermediate pressure
connector" of the control PCB.
(2) Check the resistance value of the intermediate
pressure sensor.
E82
Refrigerant insuf
fi
cient