About Alarms
Description of Abnormality Alarm
When the ground fault protector is activated, check insulation of the equipment and circuit, eliminate the cause, and
then supply power again.
Abnormality item
Alarm indication
External
Alarms
Compressor during abnormality
Operate/Stop
Reset method
Red
LED
Error code
High pressure abnormal (7th time), or
High pressure switch activated
●
E01
Yes
Stop
Operate either ground fault
protector, operation switch, or
controller.
Discharge gas temperature abnormal (3rd time)
●
E03
Yes
Stop
Discharge gas temp sensor abnormal
●
E04
Yes
Stop
Low pressure sensor abnormal
●
E05
Yes
Stop
High pressure sensor abnormal
●
E06
Yes
Stop
Suction gas temp sensor abnormal
○
E07
No
Operation
Discharge gas temp abnormal (1st to 2nd time)
○
E10
No
“Auto Recovery” when the discharge
temp gets 75 °C or below
Auto recovery
Inverter communication abnormal
●
E18
Yes
Stop
Operate either ground fault
protector, operation switch, or
controller.
Controller communication abnormal
○
E19
No
Operation
Ambient temp sensor abnormal
●
E23
Yes
Stop
Operate either ground fault
protector, operation switch, or
controller.
Gas cooler fan motor abnormal (1st to 9th time)
○
E27
No
Stop for 60 sec and then “Auto Recovery” Auto recovery
Gas cooler fan motor abnormal (10th time)
●
E28
Yes
Stop
Operate either ground fault
protector, operation switch, or
controller.
High pressure abnormal (1st to 6th time)
○
E31
No
Stop for 5 min and then “Auto Recovery”
Auto recovery
Refrigerant
fl
ood back alarm
○
E32
No
“Auto Recovery” when the difference
between evaporating temperature and
suction gas temperature is 5 K or over.
Unit outlet temp sensor abnormal
●
E57
Yes
Stop
Operate either ground fault
protector, operation switch, or
controller.
Gas cooler outlet temp sensor abnormal
●
E59
Yes
Stop
Inverter abnormal (1st to 9th time)
○
E60
No
Stop for 60 sec and then “Auto Recovery”
Auto recovery
Inverter over current (1st to 9th time)
○
E62
No
Stop for 60 sec and then “Auto Recovery”
Inverter overload (1st to 9th time)
○
E64
No
Stop for 60 sec and then “Auto Recovery”
Inverter step out (1st to 9th time)
○
E66
No
Stop for 60 sec and then “Auto Recovery”
PFC abnormal (1st to 9th time)
○
E68
No
Stop for 60 sec and then “Auto Recovery”
Inverter abnormal (10th time)
●
E70
Yes
Stop
Operate either ground fault
protector, operation switch, or
controller.
Inverter over current (10th time)
●
E72
Yes
Stop
Inverter overload (10th time)
●
E74
Yes
Stop
Inverter step out (10th time)
●
E76
Yes
Stop
PFC abnormal (10th time)
●
E78
Yes
Stop
Split cycle outlet temp sensor abnormal
●
E80
Yes
Stop
Intermediate pressure sensor abnormal
●
E81
Yes
Stop
Refrigerant insuf
fi
cient
○
E82
No
“Auto Recovery” when the opening of
split cycle electronic expansion valve is
175 (steps) or below.
Auto recovery
●
indicates lighting up, and
○
indicates blinking.
Red blinking LED is maintained even after auto-recovery of alarm content. Check the content by Alarm history.
Method of clearing Red LED: After correcting the abnormality content, align the rotary switch (knob) with
[OPERATION] and press
▲
button.