Operation in case of failure
Failure of sensors
In the event of termination of the sensor start all LEDs flashing at a frequency of 1 Hz. The number of flashes is the code for the
sensor that has failed. Termination sensor on the evaporator is not showing.
When a malfunction of the sensor of the cooling space, the LED blink 1-fold, then the ugasnejne for 5 seconds, after which the rate
again.
In the event of failure of the cooling space sensor is installed timing algorithm, which raises and delete
request for cooling of the cooling space to activate or deactivate the compressor:
- 15 minutes ON, 30 minutes OFF, then the fan is not operating.
Function intense freezing (SF) is in the case of cancellation of the sensor of the cooling space is blocked.
Thawing is carried out in 300 minutes of operation of the compressor.
In the event of termination sensor on the evaporator defrost is limited to 30 min.