33
−
Counter
clear
Command
pulse input
inhibit
Speed zero
clamp
The function differs depending on the control mode.
The function differs depending on the control mode.
・ With COM- open, the velocity command
is considered zero.
・ This input can be made disabled using Pr06.
30
33
26
CL
INH
ZEROSPD
SI
page 38
SI
page 38
SI
page 38
Signal
Pin
Symbol
Function
I/F
No.
circuit
Position
control
Velocity
control
Torque control
・ The command pulse input inhibit signal (input) is selected.
・ This signal can be made disabled using Pr43.
・ he internal command velocity selection 1 (input) is
valid. Use this together with the CL signal (input).
・ For details, see Pr05 (Speed Set-Up Switching) description.
・ Invalid
Pr43 value
1
0
Meaning
The INH signal (input) is disabled.
・With COM- closed, the pulse command
signal (PULSE SIGN) is enabled.
・With COM- open, the pulse command
signal (PULSE SIGN) is inhibited.
Position
control
Velocity
control
Torque control
・ Clears the position error counter. Connect
to COM- to clear the counter.
・ Use Pr4D to select the clear mode (0 = Level, 1 = Edge)
・ The internal speed selection 2 (input) is valid. Use
this together with the INH signal (input).
・ For details, see Pr05 (Velocity Set-Up Switching) description.
・ Invalid
Pr43 value
0
1
Meaning
ZEROSPD is disabled.
ZEROSPD is enabled