Signal line noise filter
Connect signal line noise filters to all cables (power cable, motor cable, operation panel remote cable
and interface cable).
Grounding
(1) To prevent an electric shock, be sure to connect the inverter’s protective earth terminal (
) with
the control panel’s protective earth terminal (PE).
(2) Two protective earth terminals (
) are provided. Do not connect these terminals together.
List of Inverters and Applicable Peripheral Equipment
Voltage
Spec.
Rated
output
Circuit breaker
(Rated current)
Noise filter
∗
1
Surge
absorber
∗
1
Signal line noise
filter
400W
750W
5A 5A
1.5kW 10A
2.2kW 15A
10A
3.7kW
5.5kW
20A
400V
7.5kW 30A
30A
R.A.V-801BXZ-4
Okaya Electric
Industries Co., Ltd.
DV0P1460
●
Recommended circuit breaker:
•
Manufacturer: SANKEN-AIRPAX Co., Ltd.
•
TYPE: IEL series
Contact at:
East Japan
+81-492-83-7575
West
Japan
+81-6-6312-8716
∗
1
For the recommended noise filters and surge absorber, see P74.