36
Protective Function
Canceling trip
First remove the cause and then reset the system by following one of the following steps.
[1] Turn off the inverter. Wait until the trip message disappears and then power
on again.
[2] Leaving the trip message displayed, connect both [I1] and [I2] to [G] for at
least 0.1 seconds.
∗
1
[3] Leaving the trip message displayed, press both
△
and
▽
switches
on the operation panel for at least 1 second.
[4] Leaving the trip message displayed, issue the trip reset command.
∗
2
* If the CPU error
occurs, cancel the trip according to the above
procedure. The trip cannot be canceled with the above [2], [3] and [4] methods.
∗
1
When [
I1/I2 function selection] is set to “I1: Run/stop” and “I2: CCW/CW”, the trip cannot be
canceled.
∗
2
This method is effective only when [
I5 function selection] or [
I6 function selection] are set
to
.