KW8M Eco-POWER METER
30
5.3.1 Output depends on integral electric power
Set the unit for pulse output (0.001/0.01/0.1/1/10/100kWh) and pulse output (transistor output) turns on
every time when integral electric power reaches the unit. (Pulse width: about 100ms)
5.3.2 Instantaneous electric power alarm
When it exceeds the setting instantaneous electric power, pulse output (transistor output) turns on in
order to notice. When it falls below, the output turns off.
5.3.3 Current alarm
When it exceeds the setting current ratio, pulse output (transistor output) turns on in order to notice.
When it falls below, the output turns off.
5.3.4 Stand-by power alarm
When it detects stand-by power (current) of the measured load, pulse output (transistor output) turns on
in order to notice.
Set current (C) and stand-by time (T) to judge stand-by power.
When the measured load is satisfied the setting conditions, pulse output
(transistor output) turns on in order to notice.
When it exceeds the setting value, it turns off and reset it.
You can reset the alarm by pressing <SET> with the instantaneous electric
power display.
(Working flow chart)
(kW)
Normal working Output turns ON
E
le
c
tr
ic
pow
er
T
Set value(C)
Stand-by mode
0
Time
(Min)
5.3.5 Output depends on count value
Set the preset value and pulse output (transistor output) turns on the time when count value reaches
the preset value.
Refer to the next in detail.
5.3.6 Demand alarm
Refer to the next in detail.