9. Specifications
9.1 Standard specifications
Mounting
: Flush
Setting
: Membrane sheet key
Display
PV display
: Red LED 4 digits, character size, 18 x 8 (H x W)mm
SV display
: Green LED 4 digits, character size, 13.2 x 6 (H x W)mm
Accuracy (Setting, indication)
Thermocouple : Within
0.2% of each input span
1digit or
within
2
(4 ), whichever is greater
However, for R, S input, 0 to 200 (0 to 400 ): Within
6 (12 )
B input, 0 to 300
(0 to 600 ): Accuracy is not guaranteed.
K, J, E, T, N input, less than 0
(32 ): Within
0.4% of each
input span
1digit
RTD
: Within
0.1% of each input span
1digit or
within
1
(2 ), whichever is greater
DC current, voltage: Within
0.2% of each input span
1digit
Rated input
Input type
Input range
Resolution
–200 to 1370
–320 to 2500
1 ( )
K
–199.9 to 400.0
–199.9 to 750.0
0.1 ( )
J
–200 to 1000
–320 to 1800
1 ( )
R
0 to 1760
0 to 3200
1 ( )
S
0 to 1760
0 to 3200
1 ( )
B
0 to 1820
0 to 3300
1 ( )
E
–200 to 800
–320 to 1500
1 ( )
T
–199.9 to 400.0
–199.9 to 750.0
0.1 ( )
N
–200 to 1300
–320 to 2300
1 ( )
PL-
0 to 1390
0 to 2500
1 ( )
C(W/Re5-26)
0 to 2315
0 to 4200
1 ( )
–199.9 to 850.0
–199.9 to 999.9
0.1 ( )
Pt100
–200 to 850
–300 to 1500
1 ( )
–199.9 to 500.0
–199.9 to 900.0
0.1 ( )
JPt100
–200 to 500
–300 to 900
1 ( )
4 to 20mA DC
0 to 20mA DC
–1999 to 9999
*1 *2
1
0 to
1V DC
0 to 10V DC
1 to
5V DC
0 to
5V DC
–1999 to 9999
*1
1
*1: For DC input, input range and decimal point place are changeable.
*2: 50
shunt resistor (AKT4810
,
sold separately) must be connected
between input terminals.
Input sampling period
: 0.25 seconds