Technical/Programming Manual
FT1020G3 Rev 2.2.1
85
Figure 31 Signal period set up options
Delay time, Pulse length, Pulse off and/or De-Activation, have to be set for the "Signal
period" respectively. For types 2 & 5 the x and y times must be equal and maximum 5.6s.
For types 3 & 6 the x time must be maximum 5.6s.
Note
: The different types can be used together with the different outputs according to the
following Table 11 below
Table 11 Output signal period for programmable output
In FT1020G3
COM loop units
Output
Type
S0-
S3
R0,
R1
4581
board
4583
board
I/O
unit
3361
Unit
3364
Siren, S/B &
Beacon
4477, 3379,
4383 & 4380
4582
board
Inter
locking
1 Steady (continuous)
X
X
X
X
X
X
X
X
X
2 Intermittent
X
X
XXX
--
--
XX
--
--
--
3 One pulse
X
X
XXX
--
--
--
--
--
--
4 Steady (continuous),
delayed activation
X
X
X
X
X
X
X
X
X
5 Intermittent,
delayed activation
X
X
XXX
--
--
XX
--
--
--
6 One pulse,
delayed activation
X
X
XXX
--
--
--
--
--
--
7 Steady (continuous),
delayed de-activation
X
X
X
X
X
X
X
X
--
Содержание Firetracker FT1020G3 CIE
Страница 1: ...Technical Programming Manual FT1020G3 Rev 2 2 1 For Software V2 2 x FT1020G3 CIE M435 February 2016 ...
Страница 2: ...This page has deliberately been left blank ...
Страница 187: ...Technical Programming Manual FT1020G3 Rev 2 2 1 184 Figure 60 FT1020G3 General arrangement ...
Страница 188: ...Technical Programming Manual FT1020G3 Rev 2 2 1 185 Figure 61 FT1020G3 Block Wiring Overview ...
Страница 189: ...Technical Programming Manual FT1020G3 Rev 2 2 1 186 Figure 62 FT1020G3 Standard Block Wiring Diagram ...