Technical/Programming Manual
FT1020G3 Rev 2.2.1
37
C O M
C O M
N /O
N /O
N /O
N /O
C O M
C O M
LO O P IN
LO O P IN
LO O P O U T
LO O P O U T
R e0
R e0
R e1
R e1
Z
Z
0V
0V
MO N ITO R E D
IN P U T
MO N ITO R E D
IN P U T
FA N S TO P
R E LA Y
FA N S TA R T
R E LA Y
R L1
R L1
R L2
E O L
C A P
E O L
C A P
470n
470n
470R
470R
I/O MODULE
3361
I/O MODULE
3361
24V D C / A C
24V D C / A C
STANDARD MODE
FA N S TA R T / S TO P
R E LA Y
P R E S . S W ITC H O R C T
FA N S TA TU S
P R E S . S W ITC H O R C T
FA N S TA TU S
ENHANCED MODE
Figure 13 AS1668 Fan Control Example
6.2
Zone control
The Zone Control Module provides a simplified indication of zone status without the need
for a liquid crystal display. The disable control allows a specific zone to be temporarily
disabled without the need to access the CIE menu. This is typically used where building
works or maintenance procedures are being carried out in a localised area of a building.
The front display layout is shown as part of Figure 14 below.
Each zone control module consists of a universal I/O matrix 4582 plugged in a display
board SUB900 specifically configured to provide up to 12 individual zone indicators and
controls. The module is normally mounted in the CIE. but it is also possible to connect the
module externally via a COM loop and 24V
DC
supply.
6.2.1
Controls & Indications
Alarm LED
(Red)
– Illuminates when an alarm from a conventional zone, an addressable
device or group of addressable devices designated as a zone enters into an alarm state.
Fault LED
(Amber)
– Illuminates when either a short circuit or open circuit fault on a
conventional zone line input or any fault that prevents an addressable alarm point in a
designated zone to operate properly.
EBL512
I/O Matrix
board
COM loop
24VDC
3361
Fan
3361
Fan
3361
Fan
3361
Fan
Fan control
board
Or 24VDC from
external source
Fault
Fault
Fault
Fault
Running
Running
Running
Running
Stopped
Stopped
Stopped
F
F
F
F
A
A
A
A
N
N
N
N
On
On
On
On
Auto
Auto
Auto
Auto
Off
Off
Off
Off
Fan
Reset
LED
Test
Stopped
1668 FAN CONTROL
Содержание Firetracker FT1020G3 CIE
Страница 1: ...Technical Programming Manual FT1020G3 Rev 2 2 1 For Software V2 2 x FT1020G3 CIE M435 February 2016 ...
Страница 2: ...This page has deliberately been left blank ...
Страница 187: ...Technical Programming Manual FT1020G3 Rev 2 2 1 184 Figure 60 FT1020G3 General arrangement ...
Страница 188: ...Technical Programming Manual FT1020G3 Rev 2 2 1 185 Figure 61 FT1020G3 Block Wiring Overview ...
Страница 189: ...Technical Programming Manual FT1020G3 Rev 2 2 1 186 Figure 62 FT1020G3 Standard Block Wiring Diagram ...