EF-S1C

Electrostatic Sensor Controller

7

NAVI MODE

RUN MODE

6

PART DESCRIPTION

2

MODE key

Jog switch

MODE indicator /

PRO(Yellow)

Digital display (Green, Red)

MODE indicator / DIST (Yellow)

MODE indicator /

HOLD(Yellow)

MODE indicator / RUN (Green)

Output 1 operation indicator (Orange)

Select 1 indicator (Yellow)

Output 2 operation indicator (Orange)

Select 2 indicator (Yellow)

 MODE indicator / CUSTOM (Yellow)

MODE indicator / TIMER (Yellow)

Timing indicator

(Green)

1

2 3

Thank  you  very  much  for  using  Panasonic  products.  Please  read  this  Instruction 

Manual  carefully  and  thoroughly  for  the  correct  and  optimum  use  of  this  product. 

Kindly keep this manual in a convenient place for quick reference.

٨
٨

Never use thisproduct with adevice for personnel protection.

In case of using devices for  personnel protection, use products

which meet laws or standards, such as OSHA, ANSI or IEC etc., for

personnel protection applicable in each region or country.

WARNING

How to mount the sensor head

Ԙ

ԙ

Insert the sensor head connector into the inlet until it

clicks.

Fit the cover to the connector.

MOUNTING

3

Take care that if the front part is lifted without pushing the

controller  forward, the hook on  the rear portion  of the

mounting section islikely to break.

Note:

How to remove the controller

Ԙ
ԙ

Push the controller forward.

Lift up the front part of the controller to remove it.

Ԙ

ԙ

Ԙ

ԙ

Fit the rear part of the mounting section of the controller

on a 35mm width DIN rail.

Press down the rear part of the mounting section of

the unit on the 35mm width DIN rail and fit the front

part of the mounting section to the DIN rail.

How to mount the controller

Ԙ

ԙ

Ԙ

Sensor head

connector

Cover

ԙ

35mm width DIN rail

OUTLINE

1

٨

٨

This product can be used in combination with a exclusive sensor head (

EF-S1HS

)

(optional) to monitor electrical potentialson object surfaces.

It can also be used together with an ionizer to check results of charge removal

processes.

٨

In this mode, the current measurement value and threshold value are displayed,

(Note 1)

 and the threshold value can be set and 0-Adjust, key lock and display

value hold and charge removal time measurement operations can be carried out.

I/O CIRCUIT DIAGRAM

4

*1

Non-voltage contact or

NPN transistor open collector

High (+V, or open): Invalid

Low (0 to +2V):Valid

or

Color code

100mA max.

100mA max.

*

1

Users' circuit

Internal circuit

Load

Load

24VDC

r

10%

(Brown) + V

(Grey) Analog output

(Black) Output 1

(Pink)Timing input / 0-Adjust input

(White) Output 2

(Blue) 0V

5V

100

ǡ

Se

ns

or

ci

rcu

it

+
-

If using together with an ionizer manufactured by Panasonic, share the 0V line of this product 

with the ground of the ionizer, and carry out 0-Adjust when doing 0V measurements.

Note:

<Pointsto note when using analog output>

Because  the  0V  lines  for  judgment  output  and

analog output are common, the analog output may

vary depending on the load current.

In order to satisfy the linearity specificationsfor the

analog output, do not use the judgment output.

٨

If the MODE key is pressed, the mode can be changed to a different mode.

٨

If 'PRO' is selected in NAVI mode, the mode changes to PRO mode.

Basic system of operation for PRO mode

PRO2

Current value save

PRO4

PRO5

Selects a function in CUST mode 

to display.

CUSTOM mode display

Allows  basic  configuration  infor-

mation to be set in a single step, 

by inputting a 8-digit code.

Coding

All settings, except for data bank, 

revert to factory settings.

Reset

PRO3

Loads  configuration  setting  from 

the data bank.

Data bank load

Saves  configuration  setting  from 

the data bank.

Data bank save 

PRO6

Output mode

Output form

Sets  the  viewing  orientation  of 

the digital display.

Display turning

PRO1

Switches among response times.

Response time change

Calibration

Analog output focus

Sets hysteresis.

Hysteresis

Sets  the  digital  display  to  turn 

ON/OFF.

ECO mode setting

This  simultaneously  displays  the 

stored  measurement  value  and 

the current measurement value.

Stored value display

Select  threshold  value  display  / 

symbol display for left digital dis-

play.

Symbol display setting

This  sets  the  focus  for  analog 

output.

This calibrates the measurement 

values.

This saves the current measure-

ment value.

Display unit setting

Select  whether  least  significant 

digit is displayed / not displayed.

(The display will not change even when the jog switch is operated.)

If window comparator mode / 2-output 

mode  is  selected,  threshold  value 

setting is carried out.

This  selects  normal  open  or 

normal close as the output.

External input setting

Select the external input function.

(Timing input / 0-Adjust)

Basic system of operation for NAVI mode

 (For details, refer to '

NAVI MODE

'.)

This indicates normal sensing

operation. The threshold value 

can be adjusted and 0-Adjust

can be carried out as well.

Run

RUN

This sets HOLD mode.

Hold

HOLD

Allows various detailed set-

tings to be configured, such as

load / save and other settings.

Pro

PRO

Configuresoperation and period

of the timer, or charge removal

time measurement function.

Timer

TIMER

This displays items that have

been set using PRO5 mode and

CUST mode display functions.

Custom

CUST

Distance / Range

DIST

This sets the measurement dis-

tance and measurement range.

Basicsystem of operation for PROmode

 (For details, refer to '

PROMODE

'.)

7

9

5

OPERATION PROCEDURE AND BASIC SYSTEM


MODE key

ޓ

Press

ޓ

Press

Turn

'+' side

'-' side

Jog switch

1

3

2

Switching NAVI mode

Canceling while

setting isin progress

0-Adjust

Confirming menu

settings

Confirming setting

values

Moving setting menu

Changing setting values

Display value hold



Notes: 1)

2)

Judgment  output  and  analog  output  will  become  unstable  while  setting  operations  are

being carried out. After settingshave been completed, use in RUN mode.

If the power is turned off while settings are being confirmed (while the display is blinking),

the settings may not be applied correctly.

Notes: 1)

At the time of shipment, the threshold value is set to be displayed in the green (left) digital

display. When the symbol display setting is ON (refer to PRO2 mode), a symbol ("-" only)

appears in the green (left) digital display.

Press

Press

Threshould

value

Measurement

value

Press for

1 sec. or

more

Press for

2 sec. or

more

+

Displayvalue hold

4

Automatically

Automatically

Automatically

Keylock

If  the  MODE  key  and  the  jog  switch  are  pressed

together for 2 sec. or more, the key lock is canceled.

If the jog switch is turned to the '-' side for 1 sec. or

more, the hold is canceled.

Press to

+ side for

1 sec. or more

Notes: 5)

6)

This is enabled when HOLD mode is set to OFF.

Refer  to  '

EXTERNAL INPUT OPERATIONS

AND HOLD MEASUREMENT

' in  the instruction 

manual included (if using the

EF-S1

series surface

potential sensor for the first time) for details on the

operation when HOLD mode is set to ON.

Only the display value is held. Output is not held.

Press

Press:

Confirmed

+ threshold value setting screen

- threshold value setting screen

Turn

Turn

Threshold value setting

8

Notes: 2)

For  details  on  the  setting  range  for  the  threshold

value, refer to '

SETTING RANGE

'.

Automatically

0-Adjust setting (cancel)

Thissetsthe measurement value to zero (baseline).

When the MODE key is pressed once more for 1

sec. or more, 0-Adjust can be canceled.

Notes: 3)

4)

If the measurement value exceeds

r

200, 0-Adjust

cannot be carried out.

When 0-Adjust setting input has been selected as

the external input setting, 0-Adjust can be carried

out each time using the external input signal.

PRO MODE

9

Turn

Turn

Turn

Turn

4% of measurement range

1% of measurement range

Hysteresis

2% of measurement range

40

10

r

1kV range

20

80

20

0.5% of measurement range

5

10

0.2% of measurement range

2

4

r

2kV range

40

Press

Turn

(Calibration)

Press

Press

Current

measurement

value

Expected display

value

Press

Turn

Turn

Press

Press

Response time

change function

Turn

Response time
10ms
20ms
100ms
200ms
400ms
800ms

Focus

-400 to +400
-200 to +200

-2,000 to +2,000

r

2kV range

-1,000 to +1,000

-200 to +200
-100 to +100

-1,000 to +1,000

r

1kV range

-500 to +500

Analog 1 to +5V

+1 to +5V

(Note)

PRO1 mode setting

Hysteresis

function

Analog

output focus

x5

x10

None

x2

Note:

If a focus has been set for analog output, the resolution will change.

SETTING RANGE

8

٨

٨

٨

The threshold value can be set to within the following range.

Distance 8 to 20.5mm : +5 

҇

 +Threshold value 

҇

 +500

(

r

1 kV range)               -5 

҈

 -Threshold value 

҈

 -500

Distance 21 to 100mm: +5 

҇

 +Threshold value 

҇

 +1,000

(

r

2 kV range)               -5 

҈

 -Threshold value 

҈

 -1,000

0-adjust can be set to within the following range.

-200

҇

 Measurement value 

҇

 +200

Calibration can be set to within the following range.

0.5

҇

 (Display hold value / Current measurement value) 

҇

 10

Distance 8 to 20.5mm : -1,000

҇

 Measurement value 

҇

 +1,000

Distance 21 to 100mm: -1,999

҇

 Measurement value 

҇

 +1,999

RUN mode

Refer to '

PROMODE

'.

9

Refer to '

RUN MODE

'.

6

Press

Press

Press

Press

Press

Press

HOLD mode (Note 2)

:

Confirmed

Turn

DIST mode (Note 1)

:

Confirmed

Turn

r

1kV range

 / 

Setting distance range 8 to 20.5mm

r

2kV range

 / 

Setting distance range 21 to 100mm

TIMER mode (Note 3)

:

Confirmed

Without timer

OFF delay timer / Timer period
ON delay timer / Timer period
ONE-SHOT delay timer / Timer period

Turn

CUST mode

Turn

Response time change function

Refer to '

PRO MODE

 / 

PRO1 mode setting

'.

9

Calibration

Refer to '

PRO MODE

 / 

PRO1 mode setting

'.

9

Analog output focus

Refer to '

PRO MODE

 / 

PRO1 mode setting

'.

9

Data bank load setting function

Refer to '

PRO MODE

 / 

PRO3 mode setting

'.

9

Code setting function

Refer to '

PRO MODE

 / 

PRO5 mode setting

'.

9

PRO mode

HOLD mode setting

Threshold value / Measurement value

Display value during RUN mode

Threshold value / Peak value
+ peak value / - peak value
Peak value / Measurement value

8

Notes:

For details, refer to '

SETTING RANGE

'.

The values that are displayed during RUN mode will vary as shown in the table below

depending on the setting for HOLD mode. (A '  ' against the displayed value means that 

the value is negative.)

1)

2)

Measurement  distance:  Set  to  0.5mm  or 

1mm pitch

Measurement  range:  Set  automatically  in 

accordance with measurement distance

No hold
Peak hold measurement 

Ԙ

Peak hold measurement 

ԙ

Peak hold measurement 

Ԛ

This displays the items that have been set using PRO5 

mode and CUST mode display functions, and the set-

tings for these items can be changed.

:

Variable timer period

If HOLD mode is set to '         ', '          ' or '  

  ', the timer function will be automatically 

set to '         ' (no timer), and it will not be possible to change timer operation.

3)

CME-EFS1C No.0032-47V

Current value is displayed as expected value.

Current value is displayed as 1,000 or -1,000.

Only calibration is reset.

(Note 1)

Charge removal time measurement

This measures 'Charge removal time(sec.)'  from

1000 to 100 automatically and display it.

A start and a stop of the measurement are possible

with the jog switch.

Notes: 7)

This is enabled  when

TIMER  mode  is  set  to

'Charge removal time

measurement'.

Charge removal time measurement (Note 4)

When charge removal time measurement has been selected, the output operation will be 

without timer.

4)

Ex.)

Charge removal time is 1.2 sec.

INSTRUCTION MANUAL

Ramco National

800-280-6933 | [email protected]

www.panasonicsensors.com