Panasonic Eco Solutions Nordic AB
MEW01624 Rev: -
EBL128 version 2.0.x, Daily user's manual
14
5.5
Re-enable zone (B5)
Not available for users with access level / type "Information only".
Disabled zones are listed in menu H4/U1.
Re-enabling via menu B5 has higher priority than automatic re-
enabling.
NOTE!
Alarm points that have been individually disabled via menu
H2/B2 cannot be collectively re-enabled via menu B5. They have to
be individually re-enabled via menu H2/B6.
If there is nothing to re-enable,
--- List is empty ---
will be
shown.
Log in with a
User name
and
Password
for typ
Building officer
(or
Service personnel), see page 5.
H1 Perform monthly test
Scroll (or press
"2"
) to menu H2.
H2 Disable or re-enable
Press
"A"
to sub menu B1.
B1 Disable zone
Scroll (or press
"5"
) to menu B5.
B5 Re-enable zone
Press
"A"
.
L
=This is a list in which you can scroll. Select a zone.
To re-enable the selected zone press
"A"
.
When required, re-enable more zones or press
"Return"
(P9) to
menu B5.
Scroll to another menu or press
"Return"
to menu H2. Scroll to
another menu or leave the menu system by pressing
"Return"
.
Содержание EBL128
Страница 2: ...This page has deliberately been left blank...
Страница 4: ...Panasonic Eco Solutions Nordic AB MEW01624 Rev EBL128 version 2 0 x Daily user s manual 2...
Страница 39: ...Panasonic Eco Solutions Nordic AB MEW01624 Rev EBL128 version 2 0 x Daily user s manual 37 12 Revision history...
Страница 40: ...Panasonic Eco Solutions Nordic AB MEW01624 Rev EBL128 version 2 0 x Daily user s manual 38...
Страница 41: ...This page has deliberately been left blank...