EBL128 version 2.0.x, Daily user's manual
11
5.2
Disable zone-address (B2)
Not available for users with access level / type "Information only".
Up to 100
addressable alarm points (zone-address) can be individually
disabled via menu B2. Also addressable manual call points.
Log in with a
User name
and
Password
for typ
Building officer
(or
Service personnel), see page 5.
H1 Perform monthly test
Scroll (or press
"2"
) to menu H2.
H2 Disable or re-enable
Press
"A"
to sub menu B1.
B1 Disable zone
Scroll (or press
"2"
) to menu B2.
B2 Disable zone-address
Press
"A"
.
Use the keypad to type the zone number (01-99) and the address (01-
99). Press
"A"
.
The alarm point can be automatically re-enabled.
If
automatic re-enabling
shall
not
be used press
"A"
. Go to
.
If
automatic re-enabling
shall be used, press
"1"
and use the keypad
to set the time. Press
"A"
.
The alarm point (zone-address) is disabled. Press
"A"
. When
required, disable more alarm points or press
"Return"
to menu B2.
Scroll to another menu or press
"Return"
to menu H2. Scroll to
another menu or leave the menu system by pressing
"Return"
.
Содержание EBL128
Страница 2: ...This page has deliberately been left blank...
Страница 4: ...Panasonic Eco Solutions Nordic AB MEW01624 Rev EBL128 version 2 0 x Daily user s manual 2...
Страница 39: ...Panasonic Eco Solutions Nordic AB MEW01624 Rev EBL128 version 2 0 x Daily user s manual 37 12 Revision history...
Страница 40: ...Panasonic Eco Solutions Nordic AB MEW01624 Rev EBL128 version 2 0 x Daily user s manual 38...
Страница 41: ...This page has deliberately been left blank...